27
KESS Power Solutions Gmbh / www.kess.at / info@kess.at
Model
Rated voltage of the
batteries
Minimum values, fuses
(fast types)
Voltage dc
(V)
current
(a)
KESSUPS-92RT-1100
(12 V x 3) = 36 V
125
32
KESSUPS-92RT-1500
50
KESSUPS-92RT-2000
(12 V x 4) = 48 V
KESSUPS-92RT-3000
(12 V x 6) = 72 V
KESSUPS-92RT-6000
(12 V x 16) = 192 V
400
32
Tab.1: Protection features between device and battery module
Each battery module is independent from each device. it is permitted to con-
nect two devices at one and the same battery module. in parallel systems (4 to
6 kVA models) each device should be considered as single devices that works
independently.
fig. 10 shows the connection of a 6 kVA device in rack mounting with two battery
modules. for a larger number, proceed in a similar way.
fig.10: Connection with battery modules