45
KESS Power Solutions Gmbh / www.kess.at / info@kess.at
8.2.3 SETTiNGS oN ThE UPS diSPLAy
These setting are only featured in bypass or standby mode
code
Beschreibung
Lcd-anzeige
04
ECo mode
ENA: ECo mode enabled
diS: ECo modus disabled
05
Choose the highest and lowest acceptable
voltage value for the ECo mode with the
Up-button and down-button.
hLS: high loss of voltage
LLS: Low loss of voltage
06
bypass mode with shut down UPS
ENA: bypass enabled
diS: bypass disabled - No output voltage if the
UPS is shut down
07
bypass voltage range
Choose the highest and lowest acceptable voltage
value for the bypass mode with the Up-button and
down-button.
hLS: bypass highest voltage value
LLS: bypass lowest voltage value
code
Meaning
Lcd monitor
01
Choose the correct output voltage:
200 / 208 / 220 / 230 / 240 VAC
02
Converter mode
ENA: Converter mode enabled
diS : Normal UPS mode
03
output frequency
bAT 50: ouput frequency is 50 hz
bAT 60: ouput frequency is 60 hZ
when the converter mode is activated, choose
following ouput frequency:
Cf 50: ouput frequency is 50 hz
Cf 60: ouput frequency is 60 hz