7. Commissioning
7.5 Default factory settings
Set point
Significance
Range of the set values
Factory setting
Your personal
setting
E00
Master reset
E01
The device determines the
distance to the surface of
the water in cm
E02
Manual drinking water
top-up time
001 to 999 = 1 - 999 minutes
001 = 1 minute
E03
System type
000 = Aqadive
001 = Aqabull
001
E10
Tank height
050 bis 500 = 50 - 500 cm
No default setting
E11
Lower switching point USP,
drinking water top-up
000 bis 050 = 0 - 50 cm
020 = 20 cmg
E12
Upper switching point OSP 010 bis 060 = 10 - 60 cm
drinking water top-up
OSP >= USP + 1cm
021 = 21cm
E13
Backwater switching point
035 bis 485 = 35 - 485 cm
RSP
tank height >= RSP + 15cm
No pre-setting