Set point
Significance
Range of the set values
Factory setting
Your personal
setting
E20
Rainwater filter rinsing
000 = Time control inactive
000
001 = Time control active
002 = Immediate operation active, i.e.
rinsing starts immediately
E23
Time interval of the rinsing
001 bis 020 = 1 - 20 weeks
001 = 1 week
E24
Rinsing duration
001 bis 999 = 1 - 999 seconds
030 = 30 seconds
P40
Leakage probe
000 = no leakage probe installed
000
001 = leakage probe is an optical probe
002 = leakage probe is a conductivity probe
P41
Effect on drinking water
000 = no effect
000
top-up if leaking water is
001 = switch on drinking water top-up
detected
002 = switch off drinking water top-up
P42
Effect on rainwater filter
000 = no effect
000
rinsing if leaking water is
001 = switch on rainwater filter rinsing
detected
002 = switch off rainwater filter rinsing
18
7. Commissioning