7. Commissioning
20
7.6 Checking the set values:
In normal operation the "T", "
▲
" and "
▼
" but-
tons can be used to check set values.
A set value is assigned to each set point
(see default factory settings table).
Important! A master reset is performed
under set point E00. The distance to the
surface of the water is measured under
set point E01.
Simultaneously press "T", "
▲
" and "
▼
"
buttons.
An acoustic signal is emitted and E00
is displayed.
Use the "
▲
" and "
▼
" buttons to select the
required set point.
Confirm with "T" button.
The set value is displayed.
Briefly press the "T" button.
The set point is displayed again.
Press the "T" button until an acoustic sig-
nal is emitted.
The device is in normal operation.
If the "T" button is not pressed for 20 se-
conds, the device automatically switches to
normal operation. At the same time, an
acoustic signal is emitted.
7.7 Changing the set values:
In normal operation the "T", "
▲
" and "
▼
" but-
tons can be used to change set values.
A set value is assigned to each set point
(see default factory settings table).
Important! A master reset is performed
under set point E00. The distance to the
surface of the water is measured under
set point E01.