21
7. Commissioning
Simultaneously press "T", "
▲
" and "
▼
"
buttons.
An acoustic signal is emitted and E00
is displayed.
Use the "
▲
" or "
▼
" button to select the re-
quired set point.
Confirm with the "T" button.
The set value is displayed.
Use the "
▲
" and "
▼
" buttons to change the
required set value.
Press the "T" button until an acoustic sig-
nal is emitted.
The set value is saved.
The set point is displayed again.
Press the "T" button until an acoustic sig-
nal is emitted.
The device is in normal operation.
If the "T" button is not pressed for 20 se-
conds, the device automatically switches to
normal operation without saving any chan-
ges.
At the same time, an acoustic signal is emit-
ted. The device allows meaningful values
only for the tank height and switching points.
Tank height > RSP > OSP > USP.
After a mains power failure the set values
changed by you are retained.
7.8 Master reset
Important! A master reset deletes all the
set values entered by the user. Before
triggering the master reset, the whole sy-
stem must be checked for possible re-
sulting hazards. The factory setting is
stored in the switching device, BUT, the
system type setting (Aqadive or Aqabull)
is retained.
Simultaneously press "T", "
▲
" and "
▼
"
buttons.
An acoustic signal is emitted and E00
is displayed.
Press "T" button.
"– – –" appears in the display.
Simultaneously press the "
▲
" and "
▼
" but-
tons until an acoustic sound is emitted.
"HHH" appears in the display.
The master reset has been performed
and the factory setting is saved.
See item 7.1 Initial start-up for a descrip-
tion of further steps to be taken.