3. Installation and Assembly
Ill. shows grease separator for in-
stallation in the ground NS 7-35
outlet side incl. cable duct
Ill. shows grease separator for
installation in the ground NS 1-4
incl. cable duct
During ground-moving work, a PE-HD cable conduit
DN 40 (outer dia. 50 mm) must be laid. For this purpose,
the tank must be scored using a 60 mm saw cap. The
connection distance between separator and switch unit
must be kept as short as possible. Unnecessary chan-
ges of direction, particularly ones at angles greater than
45° must be avoided. The cable conduit must have a
continuous gradient to the separator. Condensation in-
side the cable conduit can be minimised through an
airtight seal on the conduit on the switch unit side. A
cable pull wire can be included for any later cable in-
stallation. The cable can be extended to a max. 60 m.
When the cable is drawn into the conduit to the switch
unit, the cable screw connection at the conduit cover
must be tightened firmly.
Then the union nut must be fixed on the end of the pipe.
4
5
°
1
5
0
1
8
0
100
Ill shows cable entry for SonicControl
Art.-Nr. 917822
Inside
Outside
45