Atfinger Technology Co.,Ltd.
KT1210W
Temperature Controller
Operating Manual
1.
Overview
•
Wide range working voltage.
•
Support delay start and time shutdown.
•
Heating or cooling mode can be set.
•
All parameters setting can be saved after short circuit.
•
high Control precision 0.1 centigrade
•
Can be used for domestic freezer, water tanks, refrigerator,
industrial chiller, steamer, industrial equipment and other
temperature-controlled system.
2.
Specifications
•
Power Supply: AC90~250V 50/60HZ/ DC12V/ DC24V
•
Temperature control range: -50~110
°
C
•
Difference Set Value: 0.1~30
°
C
•
Resolution Ratio: 0.1
°
C(-9.9-99.9); 1
°
C(other range)
•
Measurement accuracy:
±
0.1
°
C
•
Control accuracy: 0.1
°
C
•
Measuring inputs: NTC(10K0.5%) Waterproof sensor
•
Output: Relay Contact Capacity 10A/220V normally open
•
Environmental requirements: -20-70
°
C , humidity 20%
-85%RH
•
Size: 75mm(L)*34mm(W)*85mm(Depth)
•
Hole size: 71(L)*29(W)mm
•
Power consumption: Static current:
≤
35MA,attract current:
≤
65MA
3.
Wiring Diagram
Connection 1:Independent power supply for load
Connection 2:Same power supply for load
4.
Key Instruction
S
:Set key,Confirm the setting value,Entry and Set parameter.
:powr on/off, or quit the setting.
:increase value
:
decrease value
Work
:output indicator
Set
:Setting indicator
5.
Key Operation Instruction
•
In normal working status, hold
3seconds to power off,
hold
3seconds to power on.
•
In normal working status, press
S
. The led flash.Press
or
to increase or decrease the setting temperature
value. Press
S
to save it and back to normal screen.
•
In normal working status, press
S
for 3s to enter set mode.
Press
to switch from HC-A7.(see menu code). Press
S
to enter any code,press
to change code setting.
•
Both press
for
3seconds to reset the controller.
6.
Operation Instruction
•
In normal working status, the screen display
RT
(real time
temperature value).
•
①
Cooling mode:
HC set to C. use cooler as load. When
RT
≥
ST
(temperature set value) +
D
(difference value),
work indicator turn on. output relay connect. Load start to
work. When
RT
≤
ST
, work indicator turn off, output
relay disconnect, load stop working.
•
For example,set 10
℃
,difference 3
℃
,cooler work when
RT
≥
13
℃
.cooler stop when
RT
≤
10
℃
.
•
②
Heating mode:
HC set to H,use heater as load. When
RT
≤
ST
-
D
, work indicator turn on. output relay connect.
load start to work. When
RT
≥
ST
, work indicator turn off,
output relay disconnect, load stop working.
•
For example,set 10
℃
,difference 3
℃
,heater work when
RT
≤
7
℃
.heater stop when
RT
≥
10
℃
.
Code
explain
Setting
Range
Factory
Setting
HC
Heating/Cooling
H/C
C
D
Return Difference
0.1-30
2.0
LS
Set low Limit
-50
-50
HS
Set high limit
+110
110
PU
Delay Start
0-90minute 0
CA
Temp correction
-10-10
0.0
A7
Timing stop output
0-999minute 000