background image

Atfinger Technology Co.,Ltd.

KT1210W

Temperature Controller

Operating Manual

1.

Overview

Wide range working voltage.

Support delay start and time shutdown.

Heating or cooling mode can be set.

All parameters setting can be saved after short circuit.

high Control precision 0.1 centigrade

Can be used for domestic freezer, water tanks, refrigerator,
industrial chiller, steamer, industrial equipment and other
temperature-controlled system.

2.

Specifications

Power Supply: AC90~250V 50/60HZ/ DC12V/ DC24V

Temperature control range: -50~110

°

C

Difference Set Value: 0.1~30

°

C

Resolution Ratio: 0.1

°

C(-9.9-99.9); 1

°

C(other range)

Measurement accuracy:

±

0.1

°

C

Control accuracy: 0.1

°

C

Measuring inputs: NTC(10K0.5%) Waterproof sensor

Output: Relay Contact Capacity 10A/220V normally open

Environmental requirements: -20-70

°

C , humidity 20%

-85%RH

Size: 75mm(L)*34mm(W)*85mm(Depth)

Hole size: 71(L)*29(W)mm

Power consumption: Static current:

35MA,attract current:

65MA

3.

Wiring Diagram

Connection 1:Independent power supply for load

Connection 2:Same power supply for load

4.

Key Instruction

S

:Set key,Confirm the setting value,Entry and Set parameter.

:powr on/off, or quit the setting.

:increase value

:

decrease value

Work

:output indicator

Set

:Setting indicator

5.

Key Operation Instruction

In normal working status, hold

3seconds to power off,

hold

3seconds to power on.

In normal working status, press

S

. The led flash.Press

or

to increase or decrease the setting temperature

value. Press

S

to save it and back to normal screen.

In normal working status, press

S

for 3s to enter set mode.

Press

to switch from HC-A7.(see menu code). Press

S

to enter any code,press

to change code setting.

Both press

for

3seconds to reset the controller.

6.

Operation Instruction

In normal working status, the screen display

RT

(real time

temperature value).

Cooling mode:

HC set to C. use cooler as load. When

RT

ST

(temperature set value) +

D

(difference value),

work indicator turn on. output relay connect. Load start to
work. When

RT

ST

, work indicator turn off, output

relay disconnect, load stop working.

For example,set 10

,difference 3

,cooler work when

RT

13

.cooler stop when

RT

10

.

Heating mode:

HC set to H,use heater as load. When

RT

ST

-

D

, work indicator turn on. output relay connect.

load start to work. When

RT

ST

, work indicator turn off,

output relay disconnect, load stop working.

For example,set 10

,difference 3

,heater work when

RT

7

.heater stop when

RT

10

.

Code

explain

Setting

Range

Factory

Setting

HC

Heating/Cooling

H/C

C

D

Return Difference

0.1-30

2.0

LS

Set low Limit

-50

-50

HS

Set high limit

+110

110

PU

Delay Start

0-90minute 0

CA

Temp correction

-10-10

0.0

A7

Timing stop output

0-999minute 000

Reviews: