EN
22
The control unit is set for the radio control
of all Key
Automation transmitters.
Press”+” to display “5”
Press”+” to display “7”
Press”+” to display “6”
Photocell is always active
in closing
Press “P”, on the display ‘1”
flashes, to indicate that the set
radio decoding is ROLLING CODE
(default setting); if 2 is selected on
the display the set radio decoding
is FIX CODE
Press “+” o “-” to select the
desired type of decoding
Press the key “P” to show “5”,
and save the settings.
4.13
Photocell Function Setting
(Default setting on “0”)
Press “P”, the display shows 0,
to indicate that the photocell is
not active during opening
(default setting)
Press”+”, the display shows 1, to
indicate that the photocell is ac-
tive during opening
Through this function with the door closed and photocell interrupted, it is possible to enable/disable the opening command
Press “P” again to save the
settings
4.14
Setting of the duration of automatic closure
(Default settlng:”off”)
Press “P” to show “0”, the func-
tion is not active (default setting)
Press”+” to show “1” and activate
the function. The duration auto
-
matic closing is 5 seconds.
Press “+”,or “-” to select the dura-
tion following the table below
Press “P” again to save the set-
tings.
4.12
Setting reception mode
4.15
Setting of alarm for 2000 operating cycles
(Default setting :”off”)
Press”+” to display “8”
Press “P”. The display shows 0
to indicate that the function is not
active (default setting)
Press “+”. The display shows 1 to
indicate that the function is active
Press “P” again to save the
settings
Silencing the acoustic alarm: power off, then power on again, or press the door control keys + or - for 5 seconds
Value
0
1
2
3
4
5
6
7
8
Time
not active
5 sec
10 sec
20 sec
30 sec
60 sec
120 sec 180 sec 240 sec
Note: in order to exit the programming and save the parameters push P button for 5 seconds.
Note: in order to exit the programming and save the parameters push P button for 5 seconds.
Note: in order to exit the programming and save the parameters push P button for 5 seconds.
Note: in order to exit the programming and save the parameters push P button for 5 seconds.