System Description 1
AC Output Ratings
SL1201A
SL1202A
SL1203A
SL1212A
SL1213A
Voltage range (rms)
0 … 600
V
L-L
AC resp. 0 … 346
V
L-N
0 … 1200
V
L-L
AC resp. 692
V
L-N
Output phase
L1, L2, L3, N, PE
~ Configuration
1-phase, 2-phase, 3-phase
1-phase@3xpower, connected outside in parallel
Output specifies cable length
10 m
Prog. Voltage resolution
0.1 V
rms
Prog. voltage accuracy
0.25% FS
Max. current (autoranging) rms
3
63
A
63
A
125
A
32
A
65
A
Current @ max. voltage
3
28.9
A
43.3
A
86.6
A
21.1
A
43.2
A
Max. current (parallel connection of
the load lines at the output) rms
3
189A
189
A
375
A
97.5
A
195
A
Max. power
3
±30
kVA
±45
kVA
±90
kVA
±45
kVA
±90
kVA
Max. power / per phase
±10
kVA
±15
kVA
±30
kVA
±15
kVA
±30
kVA
Fundamental frequency
40 … 75
Hz
Measurement value acquisition
Measurement value acquisition
(AC)
Resolution
Accuracy
Current measurement
0.1
Arms
±0.4
Arms ±0.2%
3
Voltage measurement
0.01
Vrms
±0.25
Vrms ±0.15%
Programmable voltage
0.1
Vrms
0.25% FS
Supplemental Characteristics
AC Output Rating
Resolution
Accuracy
Voltage Slew Rate
3
V/µs open circuit
Progr. Frequency Slew Rate
±0.1%
Load regulation
0.25% FS
Phase Angle Setpoint
0.1 deg
1.5 deg
Progr. Frequency
0.01
Hz
±0.01%
Crest factor
up to 3.6
THD with linear load
0.25%
Leakage current
(for SL1201A/SL1202A)
14.6 mA (@ 16 A, 230 V, 750 Hz, 1 ph)
Measurement (AC)
Resolution
Accuracy
Frequency measurement
0.01
Hz
±0.04 Hz
Phase angle range 0 – 360 deg
0.5 deg
<±2 deg
AC Output peak current measure-
ment
±0.5
A ±0.5% of reading (<100 Hz)
3
Specification valid in single-phase mode