Keysight Instrument Rack E7950A-1.3m E3661B-1.6m E3662B-2.0
19
Anti-tip Stabilizer
Standard on each Keysight rack is a retractable anti-tip stabilizer mechanism.
Located at the bottom center of the rack, it provides temporary additional
stability when installing or removing equipment components. The anti-tip
stabilizer should also be used when slide-mounted components are in their
extended position.
Casters
Each Keysight rack is provided with four, 3-inch diameter, smooth rolling,
heavy-duty casters to facilitate moves over short distances.
Levelers
Levelers are located in each corner to level and stabilize the rack. For maximum
accuracy, use a level while adjusting the feet.
PDU
A 110V (option AW3) or 220V (option AW5) PDU can be ordered with each rack.
A maximum of two PDUs can be installed in one rack.
PDU Install Kit
A PDU installation kit is installed at the factory for the above PDU – each
installation kit has the capability for installation of a second PDU. A second PDU
can be ordered and installed by the customer.
Extractor Fan
An extractor fan assembly can be ordered and consists of two 100 cubic feet per
minute tube-axial fans attached to a fan tray. The fan assembly is attached to
the top-rear of the rack frame.
The stability work sheets should be used whenever a new system
is configured, or a change to a system is made, to assure rack
stability.
Use the ballast accessory (P/N C2790A) when permanent
additional stability is required. See the worksheets in Appendix A
to determine your ballast requirements.
A fully loaded cabinet's maximum gross weight of 816kg (1800 lbs)
can overload a raised floor.