3
Operating the Power Supply Locally
44
Series N5700 User’s Guide
Power Supply OK Signal
The Power Supply OK signal on the J1 connector indicates a fault
condition in the power supply. J1 pin 16 is a TTL output signal. Pins 2
and 3, which are connected internally, are the signal common. All pins
are optically isolated from the power supply output. With no fault, Power
Supply OK is high, with a maximum source current of 2mA. When a fault
occurs, Power Supply OK is low, with a maximum sink current of 1mA.
The following faults set this signal low:
Over-voltage protection
Enable/Disable signal true
Over-current protection
Shut Off signal true
Over-temperature protection
Remote interface failure
AC line failure
Output turned off
Daisy-Chained Output Shut-down
It is possible to configure a multiple power supply system to shut down
all the units when a fault condition occurs in one of the units. SW1 setup
switch 5 must be in the Down position to enable the daisy-chain
operation. Other switches are unaffected by this setting.
If a fault occurs in one unit, its Power Supply OK signal is set low and its
display will indicate the fault. The other units shut off with their displays
indicating SO. When the fault condition is cleared, all units will recover
according to their Safe-Start or Auto-Restart settings.
The following figure shows three units daisy-chained - the same
connection method can be used with additional units. The Shut Off and
Power Supply OK signals are referenced to Chassis Common (J1 pins 2
and 3).
Analog Programming of Output Voltage and Current
CAUTION
J1 pin 12, pin 22, and pin 23 are internally connected to the negative sense
terminal. Do not reference these pins to any terminal other than the negative
sense terminal, as it may damage the unit.
In Local mode, the output voltage and current is programmed with the
front panel VOLTAGE and CURRENT knobs or over the remote interface.
In Analog mode, the output voltage and current can be programmed
either by an analog voltage or by resistors connected to the rear panel J1
connector.
POWER SUPPLY
#
1
J1-2,3
J1-16
J1-16
J1-16
J1-15
Supply OK
POWER SUPPLY
#
2
J1-2,3
J1-15
POWER SUPPLY
#3
J1-2,3
J1-15
Shut Off
Com
Shut Off
Supply OK
Com
Com
Supply OK