Specifications
Appendix A
Series N8700 User’s Guide
97
Supplemental Characteristics (continued)
Model 3.3kW
5kW
N8731A
N8732A
N8733A
N8734A
N8754A
N8735A
N8755A
N8736A
N8756A
N8737A
N8757A
N8738A
N8758A
N8739A
N8759A
N8740A
N8760A
N8741A
N8761A
N8742A
N8762A
Regulatory Compliance:
EMC
Safety
Complies with European EMC Directive for test and measurement products.
● IEC/EN 61326
-1
● CISPR 11, Group 1, class A
●
AS/NZS CISPR 11
● ICES/NMB
-001
Complies with the Australian standard and carries the C-Tick mark.
This ISM device complies with Canadian ICES-001. Cet appareil ISM est conforme à la norme NMB-001 du Canada.
Complies with the European Low Voltage Directive and carries the CE-marking.
Conforms to UL 61010-1 and CSA C22.2 61010-1.
AC Input:
Nominal Input
3.3kW single-phase
3.3kW & 5kW 3-phase
3.3kW & 5kW 3-phase
Input Current
3.3kW single-phase
3.3kW 3-phase
3.3kW 3-phase
5kW 3-phase
5kW 3-phase
Input Range
Single-phase models
3-phase,
200V models
3-phase, 400V models
Input VA
3.3kW units
5kW units
Power Factor
3.3kW units
3.3kW units
5kW units
Efficiency
3.3kW units
5kW units
Inrush Current
Single-phase models
3-phase,
200V models
3-phase, 400V models
ALL Models: 190 – 240 Vac; 50/60Hz
200 Vac Models: 190 – 240 Vac; 50/60Hz
400 Vac Models: 380 – 415 Vac; 50/60Hz
ALL Models: 23 –
24A Max @ 100% load
200 Vac Models: 13.6 –
14.5A Max @ 100% load
400 Vac Models: 6.8 –
7.2A Max @ 100% load
200 Vac Models: 21 –
22A Max @ 100% load
400 Vac Models: 10.5 –
12A Max @ 100% load
170 – 265 Vac; 47 – 63 Hz
170 – 265 Vac; 47 – 63 Hz
342 – 460 Vac; 47 – 63 Hz
4000 VA
5800 VA
Single-phase models: 0.99 at nominal input and rated output power
3-phase models: 0.95 at nominal input and rated output power
3-phase models: 0.94 at nominal input and rated output power
82%
–
88%
83%
–
88%
< 50A
< 50A
< 20A