1. Recommended Locations for Smoke Alarms

• Put smoke alarms at both ends of a hallway or large room if the hall-

way or room is more than 30 ft (9.1 m) long.  For large rooms, one
smoke alarm is recommended for every 500 square feet of floor
space.

• In homes that are not well insulated, extreme heat or cold can be

transferred from the outside to the inside through poorly insulated
walls and roof. This may create a thermal barrier which can prevent
the smoke from reaching an alarm mounted on the ceiling.  If you are
not sure about the insulation in your home, or if you notice that the
outer walls and ceiling are either hot or cold, install the alarm on an
inside wall. In such homes, install the smoke alarm with the top edge
of the alarm at a minimum of 4” (10 cm) and a maximum of 12”
(30.5 cm) below the ceiling (see FIGURE 1).

• Install Smoke Alarms on sloped, peaked or cathedral ceilings at or

within 3ft (0.9m) of the highest point (measured horizontally).  NFPA
72 states: “Smoke alarms in rooms with ceiling slopes greater than 1
ft in 8 ft (.3m in 2.4 m) horizontally shall be located on the high side
of the room.” NFPA 72 states: “A row of detectors shall be spaced
and located within 3 ft (0.9m) of the peak of the ceiling measured
horizontally” (see FIGURE 2).

• Install Smoke Alarms on tray-shaped ceilings (coffered ceilings) on the

highest portion of the ceiling or on the sloped portion of the ceiling
within 12” (305mm) vertically down from the highest point (see FIG-
URE 4).

Mobile Home Installation

Modern mobile homes have been designed and built to be energy effi-
cient. Install smoke alarms as recommended above (refer to RECOM-
MENDED LOCATIONS and FIGURE 1 and 2). In older mobile homes that
are not well insulated compared to present standards, extreme heat or
cold can be transferred from the outside to the inside through poorly
insulated walls and roof. This may create a thermal barrier which can
prevent the smoke from reaching an alarm mounted on the ceiling. In
such units, install the smoke alarm on an inside wall with the top edge
of the alarm at a minimum of 4” (10cm) and a maximum of 12”
(30.5cm) below the ceiling (see FIGURE 1).

If you are not sure about the insulation in your mobile home, or if you
notice that the outer walls and ceiling are either hot or cold, install the
alarm on an inside wall. For minimum protection, install at least one
alarm close to the sleeping rooms. For additional protection, see SINGLE
FLOOR PLAN in FIGURE 2.

WARNING: TEST YOUR SMOKE ALARM OPERATION AFTER

RV OR MOBILE HOME VEHICLE HAS BEEN IN STORAGE, BEFORE
EACH TRIP AND AT LEAST ONCE A WEEK DURING USE.

!

0930-7206-02_EN:_  2017.4.6  4:10 PM  Page 6

Summary of Contents for 0915E

Page 1: ...this User Guide which should be saved for future reference and passed on to any subsequent owner Smoke Alarm User Guide i9040 and i9040RV 9 Volt Battery Operated Model i9030 i9040 i9040RV i9050 i9060...

Page 2: ...with all family members Alert small children in the home Leave immediately by your escape plan Every second counts so don t waste time getting dressed or picking up valuables In leaving don t open an...

Page 3: ...F BATTERY WILL RENDER THE SMOKE ALARM INOPERATIVE WARNING TEST YOUR SMOKE ALARM OPERATION AFTER RV OR MOBILE HOME VEHICLE HAS BEEN IN STORAGE BEFORE EACH TRIP AND AT LEAST ONCE A WEEK DURING USE CAUTI...

Page 4: ...alarm detects products of combustion using the ionization tech nique It contains 0 9 microcurie of Americium 241 a radioactive materi al see section 9 Distributed under U S NRC License No 32 23858 01...

Page 5: ...ing the sleeper Smoke heat and combustion products rise to the ceiling and spread horizontally Mounting the smoke alarm on the ceiling in the center of the room places it closest to all points in the...

Page 6: ...easured horizontally see FIGURE 2 Install Smoke Alarms on tray shaped ceilings coffered ceilings on the highest portion of the ceiling or on the sloped portion of the ceiling within 12 305mm verticall...

Page 7: ...fested areas Smoke alarms should not be installed within 3 ft 9m of the following the door to a kitchen the door to a bathroom containing a tub or shower forced air supply ducts used for heating or co...

Page 8: ...acket shown mounting bracket for all other models 5 When wall mounting mount flat side to the wall and rotate mount ing plate approximately 5 to the right as shown The A line should be hori zontal and...

Page 9: ...CAUTION IF THE BATTERY REMINDER FINGER IS NOT HELD DOWN IN THE BATTERY COMPARTMENT BY THE BATTERY THE BAT TERY DOOR WILL NOT CLOSE AND THE UNIT WILL NOT ATTACH TO THE MOUNTING BRACKET NOTE THE I9030...

Page 10: ...ombustion are still present The HUSH feature can be used repeated ly until the air has been cleared of the condition causing the alarm NOTE DENSE SMOKE WILL OVERRIDE THE HUSH CONTROL FEA TURE AND SOUN...

Page 11: ...tion of the OFF arrow on the cover see FIGURE 8 i9030 i9040 i9050 i9060 and i9080 Smoke Alarms are powered by a 9V carbon zinc battery alkaline batteries may also be used A fresh bat tery should last...

Page 12: ...d with a damp cloth After cleaning reinstall your alarm and test your alarm by using the test button If cleaning does not restore the alarm to normal operation the alarm should be replaced LED SAFETY...

Page 13: ...ionization alarms A battery powered alarm must have a battery of the specified type in good condition and installed properly AC powered alarms without battery backup will not operate if the AC power...

Page 14: ...order to execute the escape plan Practice allows all occupants to test your plan before an emergency You may not be able to reach your children It is important they know what to do Install and maintai...

Page 15: ...ces and unfinished attics 5 In the living area s of a guest suite 6 In the living area s of a residential board and care occupancy small facility Are More Smoke Alarms Desirable The required number of...

Page 16: ...to enable detection of visible and invisible combustion products The radioactive element is safely contained in the chamber and requires no adjustments or mainte nance This smoke alarm meets or exceed...

Page 17: ...S PARENT OR SUBSIDIARY CORPO RATIONS ARISING FROM THE SALE OF THIS SMOKE ALARM OR UNDER THE TERMS OF THIS LIMITED WARRANTY SHALL NOT IN ANY CASE EXCEED THE COST OF REPLACEMENT OF SMOKE ALARM AND IN NO...

Page 18: ...NS OR FOR MORE INFORMATION Call our Consumer Hotline at 1 800 880 6788 or contact us at our website at www kidde com Kidde 1016 Corporate Park Drive Mebane NC 27302 0930 7206 02_EN _ 2017 4 6 4 10 PM...

Reviews: