background image

06-235793-001

December 2001

Scorpio

3

interface switches and indicators are located on the op-
erator interface board behind the locked cover. The en-
closure is of sufficient size to house the two 1.2 V 1.2 AH
batteries required for standby power operation.

*

An optional dead-front enclosure (P/N 06-235500-001)
is available (mandatory for use in Canada). The dead
front protects the user from access to any exposed
wiring. See Figure 1 for installation.

Four (4)

Mounting Screws,

P/N 06-250354-071

Figure 1. Dead Front Enclosure

PROGRAMMING

The control panel provides an 8 position DIP switch (S2)
for setting of the programmable functions of the unit. These
functions are set by placing the switch in either the ON or
OFF position. The following paragraphs explain the func-
tions and appropriate settings.

S2-1.

 Switch 2-1 allows the installer to program the con-

trol unit to activate the release output on activation of one
alarm zone or both alarm zones (cross-zoned). S2-1 OFF
= 2 zone release (cross-zoned), S2-1 ON = 1 zone re-
lease.

S2-2.

 Switch 2-2 is not used.

S2-3. 

Switch 2-3 allows the installer to program a delay

for the manual release input circuit. The manual input cir-
cuit may be either delayed or not delayed. The same de-
lays apply to this circuit when activated as to the detection
circuits (to a maximum of 30 seconds). S2-3 OFF = im-
mediate output, S2-3 ON = delayed.

S2-4, S2-5 & S2-6.

 Switches 2-4, 2-5 & 2-6 allow the in-

staller to program the unit with the appropriate delay (0, 10,
20, 30, 40, 50 or 60 seconds), needed for the installation.
Table 3 lists the switch positions and associated delays. (The
manual release delay will delay for 30 seconds, maximum.)

Note:

Panels with software revision 06-235252-002 or ear-
lier, made prior to date code 9735, S2-6 = ON En-
ables the abort function, S2-6 = OFF Disables the
abort function.

S2-7 & S2-8. 

Switches 2-7 and 2-8 allows the installer to pro-

gram the desired Abort mode for the installation. There are three
modes of Abort as explained in a previous section of this docu-
ment. S2-7 OFF = Mode 1, S2-7 ON = Mode 2, S2-8 OFF = IRI
Mode, S2-8 ON = Mode 1 or Mode 2 per S2-7.

Mode 2 and IRI Mode does not comply with UL 864.

Table 3. Switch Settings

y

a

l

e

D

e

m

i

T

4

S

5

S

6

S

.

c

e

s

0

F

F

O

F

F

O

F

F

O

.

c

e

s

0

1

N

O

F

F

O

F

F

O

.

c

e

s

0

2

F

F

O

N

O

F

F

O

.

c

e

s

0

3

N

O

N

O

F

F

O

.

c

e

s

0

4

N

O

F

F

O

N

O

.

c

e

s

0

5

F

F

O

N

O

N

O

.

c

e

s

0

6

N

O

N

O

N

O

ISOLATE SWITCH

W1 & W2.

 W1 & W2 are wire jumpers which allow the

installer to enable the use of the isolate switch (S4). To
enable the isolate switch cut 

both W1 & W2

. When both

jumpers are installed the isolate switch will not disable the
release output circuit from activating the attached sup-
pression system.

PROGRAMMABLE ALARM RELAY

W8 is a wire jumper which allows the installer to program
Alarm Relay 2. To program the relay to activate on sec-
ond alarm, cut W-8. Alarm Relay 2 is programmed to ac-
tivate at the start of release when the wire jumper is
installed.

BASIC OPERATING INSTRUCTIONS

Standby Condition

Green POWER ON LED lit, all other LEDs and sounder
off.

Alarm Condition - Panel Programmed for One Zone
Mode

Upon receipt of an alarm from an activated detector:

Red Zone 1 or Zone 2 ALARM LED lit.

Sounder on.

Signal circuit devices are activated and on steady.

Programmed release time delay activated.

Upon receipt of an alarm from an activated manual sta-
tion:

Red Manual Station ALARM LED lit.

Sounder on.

Signal circuit devices are activated and on steady.

Programmed release time delay activated.

Operation of SILENCE switch:

Yellow SILENCE LED lit.

Sounder off.

Signal circuit devices off.

Operation of ABORT:

Yellow ABORT ACTIVATE LED lit.

Discharge is aborted ONLY when alarm is from a de-
tector, and abort is activated during programmed re-

firealarmresources.com

Summary of Contents for 151FE1

Page 1: ...Scorpio Fire Control Panel Installation Operation Maintenance Manual December 2001 TM Fire Systems P N 06 235793 001 UL Listing File No S2422 firealarmresources com...

Page 2: ...firealarmresources com...

Page 3: ...not interfere with battery and printed circuit board location Do not over tighten screw terminals over tightening may damage threads resulting in reduced terminal contact pressure and difficult with s...

Page 4: ...y trained distributors technicians The entire manual should be read and fully understood prior to installation TEST EQUIPMENT Make certain test equipment is in good operating condition Do not touch li...

Page 5: ...first alarm and is a steady output on second alarm An independent form C dry con tact is associated with each of the two alarm levels when programmed for two zone release Alarm Relay 2 may also be con...

Page 6: ...instructions LAMP TEST Use the following steps to test all LEDs on the Control Panel 1 Hold the RESET Switch down All LEDs should light up 2 Release the RESET Switch All LEDs should return to Normal T...

Page 7: ...nction S2 6 OFF Disables the abort function S2 7 S2 8 Switches 2 7 and 2 8 allows the installer to pro gram the desiredAbort mode for the installation There are three modes of Abort as explained in a...

Page 8: ...RY POWER Batteries provide 24 hour standby supervision plus 5 minute alarm load at the end of that time contingent upon detection and output limitations stated herein Panel load ing and battery standb...

Page 9: ...002 W1 W2 S4 F F O ON ISOLATE BATT XFMR ON S2 8 7 6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 NO 16 C 17 NC 18 NO 19 C 20 NC 21 NO 22 C 23 NC 24 25 26 27 28 29 30 31 1 1 1 1 1 2 2 1 ALARM 1 ALARM...

Page 10: ...etracted or SET position Electric control head P N 48650001 is designed for installation on a 487 or ECS series control head only Installation of this control head to any other device e g pressure ope...

Page 11: ...d on terminals 28 31 Open circuit fault impedance 1 7K ohms UL Compatibility Identifier Number C30FE1 Two Detection Circuits Output voltage 17 3 26 0 Vdc Max number of 2 wire smoke detectors per circu...

Page 12: ...December 2001 06 235793 001 Scorpio 8 THIS PAGE INTENTIONALLY LEFT BLANK firealarmresources com...

Page 13: ...RREV DATE 5 SYSTEM EQUIPMENT 6 PRIORITY OF COMMENT 7 USEREVALUATION MANUALIS qEXCELLENT qGOOD qFAIR qPOOR qCOMPLETE qINCOMPLETE 8 qPROBLEM qQUESTION qSUGGESTION qCOMMENT check one 9 RECOMMENDEDCHANGET...

Page 14: ...KIDDE FENWAL Inc 400 Main Street Ashland MA 01721 Attn Documentation Manager Place Stamp Here FOLD FOLD firealarmresources com...

Page 15: ...firealarmresources com...

Page 16: ...hat this product is free from defects in material and workmanship and it will repair or replace any product or part thereof which proves to be defective in workmanship or material for a period of twen...

Reviews: