E-6
06-235975-001
November 2002
Kidde Gemini II System
BLK
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 0.6 OHMS.
SOLENOID
BLU
SAFETY FUSE
WHT
+
YEL
-
MICROSWITCH
SOLENOID PART NO. 899175
S
TB6
TB6
STOPV+
STOPV-
SOLENOID PART NO. 890181
1
2
S
-
3
+
STOPV-
STOPV+
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 6.0 OHMS.
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 2.3 OHMS.
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 1.5 OHMS.
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 2.3 OHMS.
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 3.7 OHMS.
S
S
S
S
S
BLK
BLK
BLK
BLK
BLK
+
+
+
+
+
-
-
-
-
-
SOLENOID PART NO. 48650001
FM GROUP A SOLENOIDS
FM GROUP B & D SOLENOIDS
FM GROUP E & G SOLENOIDS
SOLENOID PART NO. 81-100000--001
TB6
TB6
TB6
TB6
TB6
STOPV+
STOPV+
STOPV+
STOPV+
STOPV+
STOPV-
STOPV-
STOPV-
STOPV-
STOPV-
Details of Wiring Kidde Control Heads to Stop Valve Terminals
NOTE: MAXIMUM CIRCUIT WIRING RESISTANCE IS TO BE 0.6 OHMS.
Details of Wiring FM Sprinkler Solenoids to Stop Valve Terminals
Figure E-7 (con't.) Release Circuit and Stop Valve Terminal Detail