5-2
06-235975-001
November 2002
Kidde Gemini II System
This problem will be corrected if the MCP is again re-
set, and all RHUs and RDUs reply correctly to the re-
quest by the MCP for an update.
Event Error: This will only occur if an error has occurred at
a device resulting in an unspecified event. The MCP
and any RHU or RDU associated with the "Event
Error" should be reset.
The following event messages are all similar to "Name Tag
FAIL." They will occur while using the MCP menu to change
a system setting. During the process, the MCP will send
messages to affected RHUs or RDUs. If one of these should
fail to reply, or reply incorrectly, the MCP will then generate
a trouble of the type shown below. The trouble can be re-
moved by repeating the change to the system settings that
had just been undertaken. If the RHU or RDU which cre-
ated the problem replies correctly, then the trouble will be
removed.
•
‘Config FAIL’
•
‘OpRelDatFAIL’
•
‘RegisterFAIL’
•
‘DetIPIsoFAIL’
•
‘Wflo IsoFAIL’
•
‘Supv IsoFAIL’
•
‘MRel IsoFAIL’
•
‘AbortIsoFAIL’
•
‘SnderIsoFAIL’
•
‘ReleaIsoFAIL’
•
‘OptRyIsoFAIL’
•
‘Isolate FAIL’
•
‘Stp/valvFAIL’
•
‘WalkTestFAIL’