23
Electricalinstallation
Type 8615500120-000 / 8615500130-000
2. Setting the proximity switch
The proximity switch can be set to the bottom or the top
end position. The handling of the settings differs for the
various control functions.
Electronics module
Setting screw
Jumper
Setting control function:
A and I
→
bottom end position
B
→
top end position
Home position jumper
Jumper set
Setting control function:
A and I
→
top end position
B
→
bottom end position
Fig. 12: Setting the proximity switch
Bottom end position for control function a or
top end position for control function B
→
Switch on operating voltage at the proximity switch connector.
→
Using a screwdriver, set proximity switch at the setting screw to
end position.
→
Switch off operating voltage at the proximity switch
connector.
Bottom end position for control function i
→
Connect the pilot air.
Warning!
valve moves after electrical voltage has been connected!
After connecting the electrical voltage, the actuator moves to the
set end position!
▶
Never adjust the proximity switch while the process is running!
→
Connect operating voltage at Type 8615500120-000 /
8615500130-000 and proximity switch connector.
→
Move actuator to the bottom end position.
→
Using a screwdriver, set proximity switch at the setting screw to
end position.
→
Switch off the pilot air.
→
Disconnect operating voltage at Type 8615500120-000 /
8615500130-000 and proximity switch connector.
English