Because wires have resistance, voltage drop in wires becomes greater
as the wire becomes longer or the current becomes larger. This causes
the voltage applied at the load end to be smaller. The PAS series
power supplies have a sensing function that compensates for this volt-
age drop. Compensation of up to approximately 0.6 V is available for
a single line. If the voltage drop exceeds this level, wires having a
greater cross-sectional area should be used.
Table 3-2 Nominal cross-sectional area of cables and
allowable currents
Withstand voltage of load cables
For load cables, use cables with a higher voltage rating than the isola-
tion voltage of the unit. In particular, if the rated voltage of load
cables is lower than the isolation voltage of the power supply having a
rated output voltage of 40 V or more, electric shock may occur.
For details on the isolation voltage and the insulation, see "2.5
Grounding the Output Terminal"
Nominal cross-
sectional area
[mm]
AWG
(Reference
cross-sectional
area) [mm]
Allowable cur-
rent
*1
[A]
(Ta = 30°C)
*1.
Excerpts from Japanese laws related to electrical equipment.
Current recom-
mended by
Kikusui [A]
2
14
(0.28)
27
10
3.5
12
(3.31)
37
-
5.5
10
(5.26)
49
20
8
8
(8.37)
61
30
14
6
(13.3)
88
50
22
4
(21.15)
115
80
30
2
(33.62)
139
-
38
1
(42.41)
162
100
50
1/0
(53.49)
190
-
60
2/0
(67.43)
217
-
80
3/0
(85.01)
257
200
100
4/0
(107.2)
298
-
125
-
-
344
-
150
-
-
395
300
200
-
-
469
-
Summary of Contents for PAS 10-105
Page 10: ...VIII PAS SERIES This page has been intentionally left blank ...
Page 54: ...3 22 Basic Operation PAS SERIES This page has been intentionally left blank ...
Page 78: ...4 24 Remote Control PAS SERIES This page has been intentionally left blank ...
Page 131: ...PAS SERIES Specifications 8 13 This page has been intentionally left blank ...
Page 137: ...PAS SERIES Specifications 8 19 This page has been intentionally left blank ...
Page 145: ......