Item
Specification
Operational Temperature Range
32° to 113°F (0° to 45°C)
Peak Discharge Current (3s)
500 A
Peak Discharge Power (3s)
25k W
Recommended Floating Charge Voltage
52.8 V
Self-Discharge Rate
≤3% per month, ≤15% per year
• Note: This rate is only achieved when the
KiloVault® HAB™ is put to sleep by pressing
down the Power button for
3 seconds.
• The KiloVault® HAB™ will automatically shut
down after 15 minutes of no activity.
Item
Specification
Operational Temperature Range
Indoors away from direct exposure to rain or sun
Operating Temperature
32° to 113°F (0° to 45°C)
Recommended Operating Temperature
59 to 95°F (15°C to 35°C)
Short Term (less than one month) Storage Tempera-
ture
-4 to 110°F (-20° to 45°C)
Absolute Maximum Altitude
13,123 feet (4000 m)
• To operate the HAB™ at 3000m, limit the
output power to max. 6.48Kw (max 120A)”
to “Between 6561 feet (2000 m) & 9843 feet
3000 m limit, the output power to 6.48 kW. Do
not operate above 4000 m
Refer to Section 6 Troubleshooting for a complete list of protection limits.