6.4. Resetting the HAB™
If necessary, you can reset the HAB™ by first turning it on using the front power button, and then
pressing and holding down the power button for 10 seconds. This will clear any alarms and protec-
tion locks. This will not reset the cycle count.
Kilovault recomends recalibration every 6 months & more frequently if they’re not being cycled.
This manual
is f
or
use b
y qualified personnel
onl
y
7.1 Technical Support
7.2 Downloads and Documentation
Downloads and documentation are available on the KiloVault® website: https://kilovault.com/
7.3 Software
The KiloVault® HAB™ iT monitoring software for iOS and Android mobile devices can be down-
loaded from both the iOS and Android app stores. There is not a desktop version of KiloVault®
HAB™ iT.
7.4 Contact Us
Email – info@kilovault.com
Phone - +1 (888) 218-5924
KiloVault®, LLC
330 Codman Hill Road
Boxborough, MA 01719
6.5. Initial HAB™ Unboxed Voltage
If your HAB™ has a low initial voltage when unboxed, refer to the following information.
6.6. Low HAB™ voltage when unboxed
If, when you turn on your KiloVault® HAB™ , you measure a very low voltage (under 40 V) at the
battery terminals, it is in Low Voltage Hibernation. Press the front power button for three seconds
to turn the KiloVault® HAB™ off. Wait five seconds. Press and hold the power button for 10 sec-
onds. Wait five seconds. Press and hold the front power button to start the KiloVault® HAB™ .