Centauri Energy Server
–
User Manual Model Number -GF-80000-360Vdc-380Vac-3/3
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
24
INVON
System ON
no less than
0.2s
The
Energy Server
turns ON
INVOFF
System OFF
The
Energy Server
shuts
down
FAULT CLEAR
Clear faults
Press this button to clear
executed
abnormal
protection command, the
Energy Server
will restart
and run.
EPO
Emergency stop
The
Energy Server
stops
Table 12
Description of Remote-Control Signal Input
3.9 Description of Output Signal at System Dry Contact:
English Name
Chinese name
Normally Closed
Nodes
Normally Opened
Nodes
FAN FAULT
Fan fault
Fan normal
Fan fault
SYSALRAM
System alarm
No system
alarm
System alarm
GENERATOR
ON/OFF
Generator ON/OFF
Generator OFF
Generator ON
BAT LOW
Battery low voltage
No low voltage
alarm for
battery
Battery low voltage
OVERLOAD
Output overload
Output normal
Output overload
BYP FAULT
Bypass fault
Bypass input is
abnormal
Bypass fault
AC FAULT
Rectifier fault
Rectifier input is
abnormal
Rectifier fault
SYS FAULT
System fault
System is
normal
System fault
Table 13
Description of Output Signal at System Dry Contract