Centauri Energy Server
–
User Manual Model Number -GF-80000-360Vdc-380Vac-3/3
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
29
4.6 Requirements of Battery Configuration:
•
Chemical Battery:
→
The ambient temperature of the battery directly affects the service life of the battery, please
refer to the characteristic curve of
“
Service Life of Batter
y”
and
“
Environmental Temperature
”
for the environmental management. The optimal standard working temperature is 25
o
C. The
long time use of the battery in high temperature will influence the discharge time of the system
and the service life of the battery pack.
→
The battery should be kept far away from the heat source and should be provided with the
proper ventilation to avoid the generation of explosive hydrogen and oxygen mixed gas.
→
The battery switch should be installed close to the battery as much as possible and ensure that
the distance between the battery and the Energy Sever is shortest as much as possible.
•
Sirius Module:
→
Do not charge the Module when the temperature is below -30
o
C.
→
Do not charge the Module when temperature is above 80
o
C.
→
All Modules must be at 100% SOC before connecting in Series or in Parallel.
→
Modules cannot be connected in Series-Parallel combination under any circumstance.
4.7 Incoming Line Way of System:
The incoming lines of this product series are the lower wiring pattern. When making connection of
wires, open the front door of the Energy Sever, unpack the downside baffle, you will see the
connection bar connected with the power cable.
4.8 Requirements of External Protective Devices:
•
Make sure that the power of the external power supply should be more than 1.5 times of the
equipment's rated power and the rated current of the power circuit breaker supply nearby the
supply equipment should be more than 1.2 times (not the switch with one grade higher than the
breaker) of that of the air switch of the equipment itself (RECTIFIER or BYPASS).
•
The
“
BYPASS INPUT
”
and
“
AC INPUT
”
power supply system of the equipment should be equipped