Emergency Stop Operation:
In case of an emergency (such as an electric shock, a fire, a flood, etc.), please press the Red
“
EPO
”
button on the panel to execute the emergency power OFF command. After the button is pressed, the
system immediately shuts OFF all the outputs (including the Energy Sever and the bypass outputs,
battery charging or discharging). When the Energy Sever is shut down, please perform
“
power OFF
procedures”
and when the system display,
indicators are completely OFF
, perform the “Power O
N
Procedures”. Please operate carefully!
5.3
Clear Operation for System Fault:
When the Energy Sever is shut down, over-temperature of the rectifier and the Energy Sever, overload
being more than or equal to 150%, DC BUS instantaneous overvoltage, abnormal protection, etc.,
please confirm that the fault has disappeared according to the prompt of the alarm information on
the screen, and then press
“
FAULT CLEAR
”
button on the panel. The system will automatically clear
away the history faults and will restart for normal working.
5.4 Maintenance Bypass Operation:
5.4.1 Precautions:
•
Please read the safety precautions carefully and operate the maintenance bypass carefully.
Otherwise, it may damage the Energy Server or cause the load to power down, which may even
threaten personal safety.
•
In order to ensure normal use for the user, during maintenance and troubleshooting, please go to
the control panel “Inverter Settings” and set manual bypass as “ON” and then turn on
the “Manual
Maintenance Switch” and disconnect the system “Output Switch”.
Note!
The system has self-diagnosis and self-recovery functions. Within one hour, the
restriction is valid for three times. If exception persists, the system will wait for one
hour and then run automatically.