5.4.2 Entering Service Mode:
The following procedures can switch the load from being powered by Energy Server to be directly
connected to the AC input bypass power supply via the maintenance bypass switch.
1.
After the bypass parameters are detected and confirmed being normal, please do the following
steps:
•
Press
“
”
button on the main interface.
•
Go to
“USER
Settings
”
.
•
Enter
password (the default password is “87654321”
).
•
Now press
“
”
button in the main interface to enter
“
INV settings
”
•
Go to
“
Manual Bypass
”
interface to select
“
ON
”
option and click
“
YES
”
button.
At this point, the Energy Sever supplies the power to the load through the static bypass system.
2.
Remove the lock catch from
“
MANUAL BYPASS
”
air switch to turn it ON; at this point, the
maintenance bypass power supply and inverter static bypass power supply are in parallel to power
the load.
3.
Press the
“
OFF
”
button on the panel and then click
“
OK
”
button on the touch screen, the system
will shut down immediately.
4.
Manually disconnect all switches, including
“
RECTIFIER
”
,
“
BYPASS
”
,
“
DC START
”
,
“OUTPUT”, “PV
n
#”
and external
“
battery pack
”.
5.
At this moment, the operation of switching the inverter output into the maintenance bypass has
been completed. The load is driven by the maintenance bypass, the entire fans stops and the
Energy Sever is shut down completely. However, the voltage of the DC BUS inside the Energy Sever
is still high. Once the DC BUS is discharged completely, the maintenance personnel can take the
routine maintenance or repair for Energy Sever. In maintenance mode, loaded devices have no AC
power abnormal protection.
5.4.3 Exit Service Mode:
After the maintenance work is completed, the following procedures can be executed to switch the
load from the non-AC power supply abnormal protection status to the inverter power supply
protection status.