Centauri Energy Server
–
User Manual Model Number -GF-80000-360Vdc-380Vac-3/3
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
44
1) Carefully confirm that no objects are left in the Energy Sever cabinet and the internal connecting
cables of the Energy Sever are restored to the state before the maintenance.
2) Boot the system following the
“
Power ON procedures
”
, after completion, the inverter is in the
standby state and the
“
INV LED
” indicator is
flashing.
3) Turn OFF the maintenance bypass switch and put on the dismantled buckle in place.
4) Now do the following steps to exit maintenance mode:
•
Press
“
” button on the main interfac
e.
•
Go to
“
User Settings
”
.
•
Enter the password
(the default password is “87654321”)
.
•
Now press
“
” button
in the main interface to enter
“
INV Settings
”
.
•
Go to
“M
anual Bypass
”
interface successively to select
“
OFF
”
option and click
“
YES
”
button.
At this point, the maintenance steps have been completed and the load is powered up by the inverter
instead of the bypass system.
5.5 System Settings:
Click
“
”
button to enter the system setup interface.
5.5.1 Advanced Setup:
→
Click the
“
Advanced Settings
”
button and enter using the advanced password. It can only be done
by the authorized technical personnel.
5.5.1.1 System Mode settings:
•
Tap “System Settings”.
•
Go to “VERSION Settings” and select any of the versions; “DEFAULT” or “ECO” or “ON
-
GRID”. Tap
“OK” to
confirm.
Tap “VERSION Settings” → “
ON-
GRID” version. Tap “System Settings” → “Mode” → “GRID”
mode or “ANTI_C” mode
,
tap “OK” to
confirm.
“DEFAULT” version
: OFF-Grid Mode (PV UPS Mode).
“ECO” version
: ECO Mode.
“ON
-
GRID” version
: ON-GRID Mode, including ON-GRID power generation mode (GRID mode)
and anti-countercurrent mode (ANTI_C mode), it defaults to ON-GRID power generation
mode (GRID mode).