Centauri Energy Server
–
User Manual Model Number -GF-80000-360Vdc-380Vac-3/3
This manual is subject to change without notice and at the sole discretion of Kilowatt Labs, Inc.
Kilowatt Labs, Inc. |
56
AC Freq Fail
The AC frequency exceeds the
system rated value.
Adjust the system input power or wait
for recovery (short fault).
AC Phase Abnormal
The AC phase sequence is not
correctly connected.
Adjust any two phases of the system
input lines.
Bypass Over Load
Protect
When the bypass load is more
than or equal to 150%, the
bypass output will be cut OFF.
When the load shedding is less than
90%, the bypass output will be restored
by
pressing “FAULT CLEAR” button.
Inv Over Load
When the inverter load is not
less than 150% and the
overload time is finished, or the
inverter is shut down for
protection.
Output Over Load The load is more than 105%.
Get the load shedding to be less than
90%.
REC Fault
After the rectifier is started, the
rectified voltage is lower than
the system set value.
♦
Press
“
FAULT CLEAR
”
button for
recovery.
♦
If the fault still exits, please ask the local
authorized technician for service.
Bus Over Volt
High-voltage protection of DC
BUS.
BUS Soft Start Fail
The soft boot of the rectifier
fails.
Charge Fault
The charging current is larger
than the set value.
Bus Low Volt
Shutdown
The
voltage
of
battery
discharge and DC BUS is lower
than minimum set value.
The system will not automatically boot
until the AC recovers or the PV is
sufficient and the battery capacity is not
less than 90%.
Bat Low Volt
The battery voltage is lower
than the set value.
Bat EOD
The battery voltage is lower
than the minimum.