Determination of Mounting Positions:
Please pay attention to the following requirements for the selection of the Energy Serve
r’s
installation
place.
1)
The Energy Sever must be installed in clean and dry room (the environment temperature within
0 ~ 40
o
C, the relative humidity of 5% ~ 90%, and the optimal operating temperature of 25
o
C). If the
room temperature is 40
o
C, the indoor exhaust fan should be installed to ensure sufficient air flow in
the room so that the equipment gets full heat dissipation in case of the rise in room temperature. It is
best to be equipped with A/C system.
2)
To facilitate the wiring daily maintenance, diagnosis, and repair of the Energy Sever, please
make sure that the safe space of the front and the back doors is reserved (The advisable space is 1000
mm or more to ensure that the door of the Energy Sever can be fully opened, and the operators can
pass the door freely).
Fig 6 Schematic Diagram of System Installation
i.
For altitude greater than 1000 meters, the derating of the Energy Sever should be used.
ii.
The bearing capability of the pallet should be greater than the equipment weight (The
equipment weight is as shown in the technical specifications).