100
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
C2.28
Step 14 operating
time
0.0~6500.0
0.1
20.0
○
0~65000
C2.29
Step 15 setting
Same as C2.01
1
000
○
0~323H
C2.30
Step 15 operating
time
0.0~6500.0
0.1
20.0
○
0~65000
Group C3
:
Swing parameters
C3.00
Swing
function
selector
0
:
Disable
1
:
Enable
1
0
×
0~1
C3.01
Swing Operation
mode
Unit’s place of LED
:
Startup
method
0
:
Auto mode
1
:
By terminal
Ten’s place of LED
:
Swing control
0
:
Reference centre frequency
1
:
Reference max. frequency
Hundred’s place of LED
:
Swing
states storage
0
:
Save after stop
1
:
Not save after stop
Thousand’s place of LED
:
Swing
states
storage after power failure
0
:
Save
1
:
Not save
1
0000
×
0~1111H
C3.02
Preset swing
frequency
0.00Hz~Max. frequency
0.01Hz
0.00Hz
○
0~100000
C3.03
Waiting time for
preset swing
frequency
0.0~3600.0s
0.1s
0.0s
○
0~36000
C3.04
Swing amplitude
0.0%~50.0%
0.1%
0.0%
○
0~500
C3.05
Jump frequency
0.0%~50.0%
0.1%
0.0%
○
0~500
C3.06
Swing cycle
0.1~999.9s
0.1s
10.0s
○
1~9999
C3.07
Triangle wave
rising time
0.0%~100.0%(Swing cycle)
0.1%
50.0%
○
0~1000
Group d0:Status display