34
Setting
Function
Setting
Function
frequency via DI
22
Auxiliary
reference
frequency invalid
23
Reserved
24
Reserved
25
Reserved
26
Reserved
27
Preset frequency
1
28
Preset frequency 2 29
Preset frequency
3
30
Preset frequency 4 31
Acc/Dec time 1
32
Acc/Dec time 2
33
Multi-closed
loop reference 1
34
Multi-closed loop
reference 2
35
Multi-closed
loop reference 3
36
Multi-closed loop
reference 4
37
Forward prohibit
38
Reverse prohibit
39
Acc/Dec
prohibit
40
Process closed
loop prohibit
41
Switch speed
control and
torque control
42
Main frequency
switch to digital
setting
43
PLC pause
44
PLC prohibit
45
PLC stop
memory clear
46
Swing input
47
Swing reset
48~49
Reserved
50
Timer 1 start
51
Timer 2 start
53
Counter input
54
Counter clear
Introductions to functions listed in Table 6-2:
1: Forward. 2: Reverse. 5: 3-wire operation control
These are used for terminal control mode.More details
please refer to descriptions of A6.09.
3~4: Forward/reverse jog operation.
They are used to jog control of terminal control mo
de.The jog operation frequency,jog interval and jog
Acc/Dec time are defined by A2.04~A2.05,A4.05~A
4.06.
6: External RESET signal input.
The drive can be reset via this terminal when the drive
has a fault. The function of this terminal is the same with
that of RST on the panel.
7: External fault signal input.
If the setting is 7, the fault signal of external equipment
can be input via the terminal, which is convenient for the
drive to monitor the external equipment. Once the drive
receives the fault signal, it will display “E015”.
8. External interrupt signal input
If the setting is 8, the terminal is used to cut off the
output and the drive operates at zero frequency when the
terminal is enabled. If the terminal is disabled, the drive
will start on automatically and continue the operation.
9: Drive operation prohibits.
If terminal is enabled, the drive that is operating will
coast to stop and is prohibited to restart. This function is
mainly used in application with requirements of safety
protection.
10: External stop command.
This stopping command is active in all control
modes.When terminal 35 is enabled; the drive will stop
in the mode defined in A1.05.
11: DC injection braking command.
If the setting is 11, the terminal can be used to perform
DC injection braking to the motor that is running so as to
realize the emergent stop and accurate location of the
motor. Initial braking frequency, braking delay time and
braking current are defined by A1.06~A1.08. Braking
time is the greater value between A1.09 and the effective
continuous time defined by this control terminal.
12: Coast to stop.
If the setting is 12, the function of the terminal is the
same with that defined by A1.05. It is convenient for
remote control.
13~14: Frequency ramp UP/DN.
If the setting is 13~14, the terminal can be used to
increase or decrease frequency. Its function is the same