36
Through the On/Off combinations of terminal 1 and 2,
Acc/Dec time 1~4 can be selected.
33
~
36: Reserved.
37: Forward prohibit.
The drive will coast to stop if the terminal activate when
running forward.If the terminal activate before the drive
run forward,the drive will run in 0Hz.
38: Reverse prohibits.
The drive will coast to stop if the terminal activate when
running reverse.If the terminal activate before the drive
run reverse,the drive will run in 0Hz.
39: Acc/Dec prohibit
Keep the mortor from the controlling of external signal
(except the STOP command), so the the motor can runs
at the current speed.
40:Process closed loop prohibit
Forbid process closed loop control.
41:Reseverd
42:Main frequency switch to digital setting
Switch the main frequency selector to digital setting.
43:PLC pause
Pause PLC function control.
44:PLC prohibit
Forbid PLC function running.
45:PLC stop memory clear
Clear the memory which store the steps before PLC
function stop.
46:Swing input
When this signal is valid,the drive will start swing
operation.This function is only valid when the swing
operation mode is set as 1.
47:Swing reset
When this signal is valid,it will clear swing status
information.When this signal is invalid,the drive will
start swing function again.
A6.08 Terminal filter
0
~
500ms
【
10ms
】
A6.08 is used to set the time of filter for input
terminals.When the state of input terminals change,it
must keep the state for the filter time,or the new state
won’t be valid.
A6.09 Terminal control mode
selection
0
~
3
【
0
】
This parameter defines four operating modes controlled
by external terminals.
0: 2-wire operating mode 1
Fig.6-19 2-wire operating mode 1
1
:
2-wire operating mode 2
Fig.6-20 2-wire operating mode 2
2
:
3-wire operating mode 1
Fig.6-21 3-wire operating mode 1
Where:
SB1: Stop button
SB2: Run forward button
SB3: Run reverse button
Terminal Xi is the multi-function input terminal of
X1~X5.At this time, the function of this terminal should
be defined as No.5 function of “3-wire operation”.
3
:
3-wire operation mode 2
CV100