42
A6.35 AI2 filter
0.01
~
10.00s
【
0.05
】
A6.36
Reserved
A6.34
~
A6.36 define the time constant of AI filter.The
longer the filter time,the stronger the anti-interference
ability,but the response will become slower.The shorter
the filter time,the faster the response,but the
anti-interference ability will become weaker.
A6.37 Analog input zero
offset calibration
0~1
【
0
】
0:Disable calibration
1:Enable calibration
Note:
Make sure there is no input signal to AI terminal or
short-circuit AI and GND terminals when enabling
calibration.
A6.38 Gain of AI1
0.00%~200%
【
110%
】
A6.39 Gain of AI2
0.00%~200%
【
110%
】
A6.40~A6.43 Reserved
0.00%~200%
【
110%
】
AI input gain is used to adjust the corresponding
relationship between external input and internal
value.When increasing the value of AI gain,the
corresponding internal value will also increase,vice
versa.It can adjust the relationship between analog input
and setting frequency by using together with A6.37.
A6.44 Setting value of timer 1
0.0~10.0s
【
0
】
A6.45 Setting value of timer 2
0~100s
【
0
】
These parameters are used for target value for timer 1
and 2,they are used together with function 51 and 52 in
Xi terminal.
A6.46 Counter target value
0~65535
【
100
】
A6.47 Counter intermediate
value
0~65535
【
50
】
6.8 Group A7
The parameters in this group are reserved
6.9 Group A8
A8.00 Protective action of relay 0
~
1111H
【
0000
】
A8.01 Fault masking selection 1 0
~
2222H
【
0000
】
A8.02 Fault masking selection 2 0
~
22H
【
00
】
Please set the fault masking selection
function carefully,or it may cause worse accident,bodily
injury and property damage.
A8.03 Motor overload protection
mode selection
0
、
1
、
2
【
1
】
0: Disabled
Attention
!