58
C3.01
Swing Operation
mode
0~1111H
【
0000
】
C3.02 Main reference
frequency
-
300.0
~
300.0Hz
【
0.00
】
C3.03 Waiting time for
preset swing frequency
0.0
~
3600.0s
【
0.0s
】
C3.02 is used to set the operating frequency of swing
operation.C3.03 is used to set the continuous time of
preset swing frequency,C3.03 is invalid when swing
operation mode is set as 1.
C3.04 Swing amplitude
0.0%~50.0%
【
0.0%
】
Swing amplitude setting value is the percentage corresponding to
centre frequency or max. frequency.
For centre frequency: Swing amplitude frequency=centre
frequency * C3.04.
For max. frequency: Swing amplitude frequency=Max. frequency
* C3.04.
C3.05 Jump frequency
0.0%~50.0%
【
0.0%
】
As shown in Fig.6-53,when C3.05 is set to 0,then there is no
jumping frequency.
C3.06 Swing cycle
0.1~999.9s
【
0.1s
】
Swing cycle is the time from rising and falling of swing
frequency.
C3.07 Triangle wave rising
time
0.0%~100.0%(Swing
cycle)
【
50.0%
】
C3.07 is the percentage corresponding to swing cycle,as shown in
Fig.6-53.
Note:
Centre frequency:It is the setting value of main reference
frequency.
Max. frequency:It is the setting value of A0.08.
6.19 Group d0
The parameters of Group d0 are used to monitor some
states of drives and motors.
d0.00 Main reference
frequency
-
300.0
~
300.0Hz
【
0.00
】
This parameter is used to monitor main reference
frequency at normal operation mode.
d0.01 Auxiliary reference
frequency
-
300.0
~
300.0Hz
【
0.00
】
This parameter is used to monitor the auxiliary reference
frequency at normal operation mode.
d0.02 Preset frequency
-
300.0
~
300.0Hz
【
0.00
】
This parameter is used to monitor the frequency
combined by main reference frequency and auxiliary
reference frequency.Positive indicates running forwards,
negative indicates running reverse.
d0.03 Frequency after
Acc/Dec
-
300.0
~
300.0Hz
【
0.00
】
This parameter is used to monitor the drive’s output
frequency(include direction) after the drive accelerating
or decelerating.
d0.04 Output frequency
-
300.0
~
300.0Hz
【
0.00
】
This parameter is used to monitor the drive’s output
frequency(include direction).
d0.05 Output voltage
0
~
480V
【
0
】
This parameter is used to monitor the drive’s output
voltage.
d0.06 Output current
0.0
~
3Ie
【
0
】
This parameter is used to monitor the drive’s output
current.
A
B
C
D
0:
Auto mode
1:
By terminal
0:
Reference centre frequency
1:
Reference max.frequency
Swing states storage
0:
Save after stop
1
:
Not save after stop
Swing states storage after power failure
0
:
Save
1:
Not save
Swing control
Startup method