Plumbing: 

 
 

 
 
 

 

The water connections for the RO-unit must meet the requirements of all  
present regulations 
 
The RO-unit must be connected to the cold water supply (max 25

o

). 

 
Install a water shut-off valve and a water meter in the raw water inlet. 
 
Maximum hardness of inlet water  25

 o

dh

 

.( compact 1) 

                       10

 o

dh

 

.( compact 2 & 3) 

 

The water inlet must be sufficiently large (at least ½”) 
 

 

 

 

 

 

 

 

 
We recommend the installation of a pressure gauge before the RO-unit to be 
able to monitor the water pressure. 

 

 
 

 

To protect the RO-

unit from dirt the enclosed ¾” micro filter must be  

installed between the inlet hose and the inlet of the RO-unit. 
  
This micro filter must be removed and cleaned every 6th month at a minimum 
or if the plumbing of the building is being repaired. 
 

 

 

The raw water meets all requirements of present regulations 

 

 

Correctly connected to cold water 

 

 

Diameter 

of inlet hose is ½” at least 

 

 

Install the filter strainer before the RO-unit 
 

 

Maximum hardness of inlet water 

25

 o

dh

 

.( compact1)

 

                                  10

 o

dh

 

.( compact 2 & 3) 

 

 
 

 

 
 
 

Summary of Contents for RO-Compact Series

Page 1: ...In n ns s st t ta a al l ll l la a at t ti i io o on n n a a an n nd d d u u us s se e er r r m m ma a an n nu u ua a al l l R R RO O O C C Co o om m mp p pa a ac c ct t t s s se e er r ri i ie e es...

Page 2: ...ate Demineralised water produced by the RO unit which is fed into the integrated storage tank Concentrate Water containing the salts and minerals extracted from the raw water Raw water Water from the...

Page 3: ...If sufficient space is not available the RO unit can also be pulled out forwards for servicing In this case a flexible hose must be used for the water connection Make room behind the RO unit for the w...

Page 4: ...ion of a pressure gauge before the RO unit to be able to monitor the water pressure To protect the RO unit from dirt the enclosed micro filter must be installed between the inlet hose and the inlet of...

Page 5: ...t exceed these limit values for chemi cal substances Fe 0 05 mg l Mg 0 02 mg l Chlorine free 0 1 mg l NTU max 1 0 Silt index SDI 3 0 Temp Max 25o C KmnO4 max 10 0 mg l Water pressure 2 7 bar In case o...

Page 6: ...ions Voltage 230 V 50 Hz Fuse 10 16 Ampere Electricity consumption 1 1 kWh compact1 2 1 7kWh Compact 3 Colour codes for connection cable wires Conductor blue 0 Conductor brown Live Conductor yellow gr...

Page 7: ...e compose The user application must have a minimum water usages of 1 l m Mount the supplied 10 mm plastic tube at the drain connection connection point 3 The drain tube is correctly connected when it...

Page 8: ...the high pressure pump switches on in order to produce permeate in the storage tank For venting the RO unit turn off the unit 3 4 times at the on off switch The RO unit is equipped with 3 level sensor...

Page 9: ...again and the pressure exceeds 1 bar the RO unit will run again automatically Slowly close the water shut off while the RO unit is still running As soon as the water supply has been completely turned...

Page 10: ...ion Rate Typical 97 98 5 97 98 5 97 98 5 Recovery Ratio 0 dh 75 75 75 Recovery Ratio 10 dh 50 50 50 Recovery Ratio 25 dh 40 Inlet Pump Brass rotary vane Brass rotary vane Brass rotary vane Inlet Motor...

Page 11: ...ry Pump multistage multistage multistage Delivery Pump 500 watts 500 watts 500 watts Power volts 230 230 230 frequency hertz 50 50 50 power kW 1 1 1 1 1 7 Fitting Connections Inlet diameter BPS SS BPS...

Page 12: ...12 1 2 3 4 5 Plumbing Hook ups Ro Compact series 5 1 3 4 2 3 1 2 3 5 4 INLET SCREEN INLET SCREEN INLET SCREEN 4 6 6 6...

Page 13: ...from storage tank 5 Electrical hook up 6 The enclosed Inlet screen must be installed between the inlet hose and the inlet of the RO unit to protect the Ro unit from dirt This micro filter must be remo...

Page 14: ...ION DENSITY INLET PRESSURE BAR INLET TEMP C PRESSURE SWITCH ENDS BAR CONCENTRATE L H HIGH PRESSURE PUMP BAR LEVEL SWITCH HIGH MEDIUM LOW PERMEATE L H CONDUCTIVITY S FEED WATER PUMP BAR FEED WATER PUMP...

Reviews: