background image

    

 Issue 

N

C.S.

04.03.20

                  Trading Estate Farnham Surrey England

Doc. No. TD 120
   

Page 8 of 25

SET UP (Continued)

5.5 Entering and Leaving Setup Mode.

 

Setup Mode is selected from Normal Mode by simultaneously pressing the UP and the SET push buttons (i.e. the two outside 
ones). This causes the LED labelled PGAIN (short for Proportional Gain) to light continuously. In Setup Mode, each of the 
parameters in the list below may be selected for adjustment by pressing the UP or DOWN push buttons as required. The 
parameter selected is indicated on the positioner circuit by an LED lighting next to the parameter's name.

                         PGAIN           -            Proportional Gain

                         DAMP            -            Damping

                         CURVE          -            Non-Linear Curve Selection

                         LOW              -            Low Current Point Calibration

                         HIGH             -             High Current Point Calibration

                         POT               -            Feedback Potentiometer Bottom of Range Setting

When the required parameter has been selected for adjustment, the SET push button is pressed to allow adjustments to be 
made – the LED next to the selected parameter starts to blink, to indicate that Adjust Mode is active. Operation in the Adjust 
Mode for each parameter is described in the following sub-sections. To leave Adjust Mode, press the SET push button again – 
this causes the LED to light continuously, and allows movement between parameters again.

Note: There is no Adjust Mode for the feedback potentiometer bottom of range setting, but the automatic end stop finding 
sequence can be initiated when this parameter is selected.

To leave set up mode (when the adjustments have been made and the SET push button pressed to leave Adjust Mode), press 
the DOWN push button repeatedly to move down the parameter's and off the end of the list – at this point the LEDs cease to 
light, and the positioner is back in Normal Mode.

5.6 Automatic Endstop Finding Procedure.

 

The positioner can automatically calibrate itself to range between any mechanical end stops (either the built-in actuator stops, or 
any external stops built into the application). During the finding sequence, the positioner moves the actuator up to the top and 
bottom stops and records their positions. It then uses these positions as the HIGH and LOW positions in the calibration data, and
applies the existing values for HIGH and LOW current input. Note that if the positioner was reverse acting before the sequence, 
it remains so after the sequence.

The End Stop Finding Sequence starts when the POT parameter is selected, and the UP and SET push buttons (i.e. the two 
outside push buttons) are pressed simultaneously. The POT LED starts to blink, and the actuator moves steadily up scale from 
its set position. When its movement is stopped by the the top physical end stop, the positioner waits briefly, then moves the 
actuator steadily downscale until it runs against the bottom physical endstop, where again it waits briefly, and finally moves 
quickly back to the set position. The calibration data is written to non-volatile memory while the actuator pauses at its bottom 
stop.

If the positioner is in service on an application where excursions to the end stops will be disruptive, avoid initiating this sequence.

5.7 Proportional Gain and Damping Settings (for Smoothness and Sensitivity).

Select Setup Mode, and the first parameter selected is automatically PGAIN – Proportional Gain. Press the SET push button, 
and the PGAIN LED will start blinking. The value of the parameter can now be increased or decreased by pressing the UP or 
DOWN push buttons as required. There are twenty nine (29) PGAIN settings which can be selected, the setting altering by a 
factor of about 1.1 each time the UP or DOWN button is pressed. The default setting lies in the middle of the range, giving 
fourteen settings above and fourteen below. Any button presses beyond the last (fourteenth) will have no effect.

Note: As soon as the UP or DOWN push button is pressed, the new PGAIN value is stored in non-volatile memory and is 
retained even if the positioner is de-energised before leaving Adjust and Setup Modes.

Title : Installation, Operation & Maintenance Instructions – Digital EL Positioner

N – AR7059 / M – AR6971 / L - AR6419 / K - AR6347 / J-AR6096 / H – AR 6082 / G – AR 5487 / F – AR 5608 / E - AR 5293

Summary of Contents for 05 EL

Page 1: ...view Electronic Settings 7 5 4 Default Settings and Reset Procedure 8 5 5 Entering and Leaving Setup Mode 8 5 6 Automatic Endstop Finding Procedure 8 5 7 Proportional Gain and Damping Settings for Smo...

Page 2: ...ched to the lid This is reproduced as Figure 10 on page 14 of this document Non IS versions carry a red label Do not use positioners with red labels in hazardous areas 2 4 Limit Switches and Proximity...

Page 3: ...or square as shown in Figure 2 b Moulded coupling versions on all direct mount versions loosen central screw in coupling shaft so that the collet is not closed and fit coupling over shaft square 3 1 5...

Page 4: ...and that the two are coupled together with a minimum of backlash any backlash acts to deteriorate the performance of the positioner actuator combination It is also essential that the 90 degree travel...

Page 5: ...ortional to the actual positioner shaft angle Like the signal supply it must also be powered through a separate 28v 300ohm barrier with parameters shown on page 16 The retransmit circuit reads the sam...

Page 6: ...crews see Figure 4 This only applies if you want to reduce the speed from its supplied maximum factory setting 5 2 Setting Limit Switch Cams Optional Equipment Limit switch cams are factory set if fit...

Page 7: ...perate as a linear device as long as it remains powered up Changing the link from on to off or vice versa while the circuit remains powered up will not cause a change from non linear to linear operati...

Page 8: ...ding sequence the positioner moves the actuator up to the top and bottom stops and records their positions It then uses these positions as the HIGH and LOW positions in the calibration data and applie...

Page 9: ...e is stored in non volatile memory and is retained even if the positioner is de energised before leaving Adjust and Setup Modes The positioner is active while adjusting the DAMP setting and continues...

Page 10: ...ode was selected irrespective of input current Press the UP or DOWN buttons to move the positioner to the angle you want to define for the High Current Point if you hold the button down continuously t...

Page 11: ...the POT LED changes from lighting continuously to blinking To set the pot first move the actuator to the downscale endstop by connecting the air supply and disconnecting the signal When it is in this...

Page 12: ...t to 12 mA for this purpose With the signal set at midway between LCP and HCP values select Adjust Mode by pressing the SET button and the CURVE LED will now blink The default curve is in fact the lin...

Page 13: ...oner The internal O ring slides to give a coarse setting and the shell mounting slots give a few degrees of fine adjustment Please note that a special version of the monitor which has an electrically...

Page 14: ...incorrect Has main feedback pot been rotated or does it need rotating because the unit has been subjected to change in direction of movement on loss of signal See section 5 11 Resetting Feedback Pot...

Page 15: ...England Doc No TD 120 Page 15 of 25 8 BASEEFA EC TYPE EXAMINATION CERTIFICATE Page 1 N AR7059 M AR6971 L AR6419 K AR6347 J AR6096 H AR 6082 G AR 5487 F AR 5608 E AR 5293 Title Installation Operation...

Page 16: ...England Doc No TD 120 Page 16 of 25 8 BASEEFA EC TYPE EXAMINATION CERTIFICATE Page 2 N AR7059 M AR6971 L AR6419 K AR6347 J AR6096 H AR 6082 G AR 5487 F AR 5608 E AR 5293 Title Installation Operation...

Page 17: ...England Doc No TD 120 Page 17 of 25 8 BASEEFA EC TYPE EXAMINATION CERTIFICATE Page 3 N AR7059 M AR6971 L AR6419 K AR6347 J AR6096 H AR 6082 G AR 5487 F AR 5608 E AR 5293 Title Installation Operation...

Page 18: ...England Doc No TD 120 Page 18 of 25 8 BASEEFA EC TYPE EXAMINATION CERTIFICATE Page 4 N AR7059 M AR6971 L AR6419 K AR6347 J AR6096 H AR 6082 G AR 5487 F AR 5608 E AR 5293 Title Installation Operation...

Page 19: ...rrey England Doc No TD 120 Page 19 of 25 Title Installation Operation Maintenance Instructions IS Digital EL Positioner 8 IECEx CERTIFICATE OF CONFORMITY Page 1 N AR7059 M AR6971 L AR6419 K AR6347 J A...

Page 20: ...rrey England Doc No TD 120 Page 20 of 25 Title Installation Operation Maintenance Instructions IS Digital EL Positioner 8 IECEx CERTIFICATE OF CONFORMITY Page 2 N AR7059 M AR6971 L AR6419 K AR6347 J A...

Page 21: ...rey England Doc No TD 120 Page 21 of 25 8 IECEx CERTIFICATE OF CONFORMITY Pages 3 4 Title Installation Operation Maintenance Instructions IS Digital EL Positioner N AR7059 M AR6971 L AR6419 K AR6347 J...

Page 22: ...urrey England Doc No TD 120 Page 22 of 25 8 IECEx CERTIFICATE OF CONFORMITY ANNEX N AR7059 M AR6971 L AR6419 K AR6347 J AR6096 H AR 6082 G AR 5487 F AR 5608 E AR 5293 Title Installation Operation Main...

Page 23: ...am Surrey England Doc No TD 120 Page 23 of 25 9 SPARE PARTS N AR7059 M AR6971 L AR6419 K AR6347 J AR6096 H AR 6082 G AR 5487 F AR 5608 E AR 5293 Title Installation Operation Maintenance Instructions I...

Page 24: ...80 CW ASP980 CW OR ASP981 CCW ASP981 CCW ASP981 CCW 7 SERVO VALVE ASSEMBLY 1 SP942 SP942 SP942 8 DIVERTER GASKET 1 SP975 SP975 SP975 9 DIVERTER BLOCK 1 SP963 SP963 SP963 10 CARRIER PLATE ASSEMBLY CONT...

Page 25: ...Item 45 See Item 45 101 M3 FULL NUT 1 See Item 45 See Item 45 See Item 45 102 M3 x 10 SLOTTED CHEESE HEAD SCREW 1 See Item 45 See Item 45 See Item 45 103 SERVO VALVE BASE GASKET 1 SP975 SP975 SP975 1...

Reviews: