36
original value set temperature in passenger zone is as follows:
If TP>TC+3,TP=TC+3;
If TP<TC-3,TP=TC-3.
The set temperature value in driver zone indicate the display
screen.
11
WIND increasing
key in passenger
zone
-
-
When pressing down left key, decrease ventilation fan speed;
when pressing down right key, thus increase ventilation fan
speed, ventilation fan’s speed could be set in scope of 1-5
gears, automatic mode in driver zone will void by manually
changing gears, thus, A/C will change into manual mode.
The minimum blower speed selected by manual style is 2th
gears to prevent evaporator from defrosting while compressor
runs. If the blower speed is less than 2th gears, the blower
speed will automatically upgrade to 2th gears once compressor
runs.
The blower speed will not be changed by manual style while
in defrosting\dehumidification mode, in the mode of
defrosting, the blower speed will be set in 5th gears.
The blower in passenger zone will run at 3th gears if the A/C
in passenger zone was not opened, however, compressor and
refrigerant feed–liquid solenoid valve in passenger zone was
opened.
The blower in Blower speed value in passenger zone indicates
in display screen.
12
WIND decreasing
key in passenger
zone
13
Clock setting key
Could set clock by pressing down clock key, adopts TEMP rotary knob in driver zone to select
“hour”, ”minute”, ”day”, “month”, “date”, and “year” etc. fields. Use TEMP rotary knob in passenger zone
to give assignment, increasing value by adjusting clockwise, decreasing value by adjusting anti-clockwise.
Confirm to clock setting by pressing clock key once more. First time start connecting battery, indicate
time: 00:00, may set clock time by clock key.
14
Auxiliary heating
setting key
Auxiliary heating consists of two working mode: timing run and direct-control run.
Timing run, the system offer to set timing: the some particular time point in a day during one week; Two
different time points in a day during one week; the some particular time point every day during one Week.
Press
auxiliary heating setting key more than 2 Sec., enter into programming interface“1”
Once more press
auxiliary heating setting key more than 2 Sec., enter into programming interface “2”