Pages 23 Total 58
Shenzhen King Pigeon Hi-Tech Co.,LED
Ver 1.2
PLC Data acquisition protocol conversion gateway
-D225
5.1.2
Configuration Software Configuration
After modifying the configuration, you need to click [Save Parameters]. After the save is successful,
click the "Restart" button to restart the device or the D225 device is powered off, power on and
restart, and the modified configuration can take effect
ote: 1. To modify the configuration, you need to log in to the configuration software, and then
configure it after selecting the device to be configured.
2.The serial port configuration is based on the FX3U serial port RS422 parameter configuration,
baud rate: 9600, data bit: 7, stop bit: 1, parity bit: EVEN
3.IP The network configuration can be modified according to your needs. When the IP mode is
static, you can specify the specific IP of the device, and when the IP mode is dynamic, the device
automatically obtains the IP
4.After the configuration is complete, you need to click [Save Parameters]. After prompting that
the save is successful, click the "Restart" button to restart the device or the D225 device is powered
off and powered on again to make the modified configuration take effect. After clicking [Save
Parameters], you can click [Read Parameters] to check whether each configuration is the modified
configuration content.
Operation steps description: (1) After logging in by selecting the device to be configured (in this
example, double-click the IP address: 192.168.1.250 to log in), select the same PLC protocol
according to the PLC connected to D225, (2) According to the connection method between PLC and
D225 , Select the link protocol, this example is that FX3U and D225 are connected through RS422
to RS232 line, so select serial port 1 (232), (3) this example selects Modbus TCP Server server
protocol, the port number can be modified or defaulted, according to According to your own needs,
(4) The serial port selection is consistent with the device link selection. The configuration of the
serial port is configured according to the parameters of the PLC serial port. (5) The device network
IP address can be modified according to your needs. (6) Click after configuration "Save parameters",
after prompting that the save is successful, you need to click the "Restart" button or the D225
device is powered off and powered on again to make the modified configuration take effect
N