background image

 

 

Pages 34    Total    58                 

Shenzhen King Pigeon Hi-Tech Co.,LED   

                                  Ver 1.2 

 

PLC Data acquisition protocol conversion gateway                           

-D225   

 

 

 

Programming software query data as follows 

 

 

The  data  collected  by  Modbus  Poll  is  exactly  the  same  as  the  data  seen  on  the  programming 
software 

 
 
 

Summary of Contents for D225

Page 1: ...PLC data acquisition protocol conversion gateway D225 D225 User manual Version V1 2 Date 7th DEC 2020 Copyright Shenzhen King Pigeon H TECH Co LTD website www 4g iot com...

Page 2: ...to copy disseminate and reprint any part of this manual in any form Violators will be held accountable by the company Disclaimer This document is only suitable for assisting readers to use this produ...

Page 3: ...ware parameter configuration 14 Steps to log in the configuration SW 14 4 1 1 Open configuration SW 14 4 1 2 Search device 15 4 1 3 Connect Device 15 Configuration software configuration instructions...

Page 4: ...VW 31 5 2 3 3 Communication connection configuration with D225 33 5 2 3 4 Comparison of the data collected by Modbus Poll and the data checked by the programming software 33 5 2 3 5 The description o...

Page 5: ...zhen King Pigeon Hi Tech Co LED Ver 1 2 PLC Data acquisition protocol conversion gateway D225 Mapping address corresponding to DL T645 1997 protocol meter 54 Mapping address corresponding to DL T645 2...

Page 6: ...in PLC data acquisition protocol on the market into Modbus TCP protocol D225 can store the PLC I O point data to the gateway through the RS 232 or RS 485 serial port of the PLC The gateway transmits t...

Page 7: ...ol conversion gateway D225 Packing list Before installing and using the D225 device please confirm whether the following materials are in the product box 1x D225 device 1x 2 bit 3 5 female connector f...

Page 8: ...D225 1x 0 5m network cable 1x Power adapter 12VDC 1A 1 x QR code label including User manual download and software information Remark If the above items are missing or damaged pls kindly contact sales...

Page 9: ...and supports wall mounted installation and DIN 35mm industrial rail installation Use configuration software to set device parameters support WIN XP WIN 7 WIN 8 and WIN 10 with a friendly interface Sup...

Page 10: ...figuration Support WIN XP WIN 7 WIN 8 and WIN 10 Network cache transmit 8Kbyte receive 8Kbyte registration package Support custom registration package Heart package Support custom heart package Certif...

Page 11: ...otal 58 Shenzhen King Pigeon Hi Tech Co LED Ver 1 2 PLC Data acquisition protocol conversion gateway D225 2 Hardware Dimensions unit mm Front view Side view left Bottom view Top view Bottom view Side...

Page 12: ...cription Power red Lighting External power suppy is normal No lighting Device fault Ethernet red Lighting Data transmission through the Ethernet port No lighting No data transmission via Ethernet port...

Page 13: ...e Data Two way data 6 green RX Receive negative 7 Brown White Data Two way data 8 Brown Data Two way data RS 485 TTL and power supply pin connector NO Function Description 1 A RS485 data A 2 B RS485 d...

Page 14: ...ort and a standard cross straight network cable is used to connect to the LAN or a standard cross network cable can be directly connected to the computer Remark If the PC is connected for the first ti...

Page 15: ...ce Search will search for all devices in the same LAN as the computer The first IP displayed for all devices is 192 168 1 250 Therefore it is best to have only one device in the LAN when the device is...

Page 16: ...in the same LAN Read Settings Read the configuration parameters of the logged in D225 device Save Settings Click this button to save all configuration parameters to the device The device must be rest...

Page 17: ...tatic IP address for the device Static IP address set device IP address Subnet mask Current Subnet mask Gateway Current gateway address DNS Server Current DNS Server Note 1 IP Address Subnet Mask Gate...

Page 18: ...ort channel Including RS232 and RS485 RS232 Baud rate Choose from 4800 9600 14400 19200 38400 56000 57600 115200 128000 9600 Data bit Choose from 7Bit 8 Bit 9 Bit 7 Bit Parity bit Choose from NONE EVE...

Page 19: ...ication protoco between device and server 1 Transparent transmission 2 KPIOT2 0 3 KPIOT3 0 4 Modbus TCP Server 5 Modbus RTU Over TCP Modbus TCP Server Port When the device is used as a TCP UDP server...

Page 20: ...he registration package the server needs to return a response packet to the device within 3 seconds otherwise it will send the registration package according to the reconnection times If the number of...

Page 21: ...eed to fill in the configuration item of Registration Package please contact our sales representative for Registration Code to fill in the content of Registration Package 3 Select Modbus TCP Server pr...

Page 22: ...e example in the picture is connected to the router and the same LAN as the computer Connection instructions 1 D225 device power cord 12V 1A 2 D225 device network cable connected to the router 3 and 4...

Page 23: ...device or the D225 device is powered off and powered on again to make the modified configuration take effect After clicking Save Parameters you can click Read Parameters to check whether each configur...

Page 24: ...merical value so select the function code as 03 For details about the function codes used to collect PLC registers please refer to Appendix Mapping address of PLC register 3 The mapping address of Mit...

Page 25: ...ox 3 Slave ID defaults to 1 because the data of Y is Boolean so the function code It is 01 for details of the function code used to collect the PLC register please refer to Appendix Mapping address of...

Page 26: ...he IP address configuration of the network settings is the same 4 fill in the port number of the D225 device note the port number must be consistent with the port configuration of the protocol paramet...

Page 27: ...ection 8 Modbus Poll Data sent TX 07 9C 00 00 00 06 01 01 13 88 00 08 07 High bit of transaction identifier 9C transaction processing identifier low 00 High bit of protocol identifier 00 low bit of pr...

Page 28: ...w byte of the length of the following byte 01 D225 device address 03 Read the function code of the register 0F start address high A0 start address low 00 The high number of acquisitions 20 Low acquisi...

Page 29: ...ple in the figure is directly connected to the D225 device through the RS485 line Note that the data A and B of the PLC RS485 port should correspond to the A and B of the RS485 interface of the D225 2...

Page 30: ...ection with D225 device 3 Server protocol selection Modbus TCP Server 4 Because PLC passes RS485 Connect with D225 so the serial port selection must be RS485 5 Configure RS485 parameters to be consist...

Page 31: ...7 data corresponding to D225 mapping address 5000 5007 so fill in the starting address as 5000 For details about the mapping address of PLC register corresponding to D225 please refer to the Appendix...

Page 32: ...Setup to pop up the configuration box 3 Slave ID defaults 1 4 Because the VW data is a 16 bit data type the function code is 03 For details on the function code used to collect PLC registers please r...

Page 33: ...s configuration of the network settings is the same 4 fill in the port number of the D225 device note the port number must be consistent with the port configuration of the protocol parameter on the co...

Page 34: ...ng Pigeon Hi Tech Co LED Ver 1 2 PLC Data acquisition protocol conversion gateway D225 Programming software query data as follows The data collected by Modbus Poll is exactly the same as the data seen...

Page 35: ...ions 08 The low number of acquisitions D225 device returns data RX 00 F4 00 00 00 04 01 01 01 81 00 high bit of transaction identifier F4 transaction processing identifier low bit 00 High bit of proto...

Page 36: ...col to Modbus protocol and supports up to 100 DL T645 1997 or 100 DL T645 2007 protocol international electric meter devices and only supports the meter address 000000000000 000000000099 The meter is...

Page 37: ...4 Select RS485 for the serial port The configuration information is configured according to the meter RS485 port parameters 5 D225 device You can choose to automatically obtain the IP address settings...

Page 38: ...he electric meter are all 03 4 The address of the electric meter in this example is 000000000000 the protocol of the electric meter is DL T645 2007 Therefore the corresponding D225 mapping address for...

Page 39: ...the address of the D225 device note the address should be the same as D225 The IP address configuration of Network Settings on the configuration software is the same 4 Fill in the port number of the D...

Page 40: ...ws click Communication of Display to view the detailed data communication information Connect to the cloud platform application instructions Take the connection to the King Pigeon KPIOT 3 0 platform a...

Page 41: ...eft blank or filled According to your own needs the company s Jin Ge 3 0 platform is fixed The heartbeat packet and the heartbeat response packet are respectively req and res 5 The serial port configu...

Page 42: ...and product name will be automatically displayed here 3 The device name is filled in according to your needs The icon can also be modified click modify to select the icon 4 fill in the timeout time ac...

Page 43: ...ABCD Choose the byte order according to how many bits of data are collected 8 You can freely choose whether To collect this data point 9 fill in the collection period according to your needs 10 if yo...

Page 44: ...You can choose the arrangement of the collected data points 3 Collect the data of FX3U output Y0 from the figure you can see that Y0 is closed 4 Collect the data of FX3U output Y7 5 Collect the data o...

Page 45: ...ing device according to the device name address and device serial number click Edit on the right 3 pop up the edit box click Add Data points or batch addition can add new collected data points or modi...

Page 46: ...LC program Take remote debugging of Mitsubishi FX3U as an example Mapping the port number setting of external network Use the port forwarding of the router to map the computer that needs to open the M...

Page 47: ...low Note To modify the configuration you need to log in to the configuration software select the device to be configured before configuring Operating instructions 1 After logging in to the device that...

Page 48: ...he company s virtual serial port software configuration is as follows Operating instructions 1 Open the virtual serial port software click the English click the Add button 2 According to the computer...

Page 49: ...RESET for more than 3 seconds until all 3 LEDs are on and then release Need to power off and restart 7 Firmware upgrade This device supports the function of directly upgrading the firmware through the...

Page 50: ...12255 01 05 State relay S S0 S4095 On off type 14000 18095 01 05 auxiliary relay M M0 M7679 On off type 34000 41679 01 05 Special Relay SM M8000 M8511 On off type 54000 54511 01 Timing register T T0...

Page 51: ...type 52000 52111 03 06 Register D D0 D7999 numeric type 4000 11999 03 06 Special Register SD D8000 D8255 numeric type 16000 16255 03 Register D for 32 bit use D0 D7999 numeric type 54000 61999 03 06 N...

Page 52: ...of Mitsubishi a maximum of 32 mapping addresses for each register collection at a time Modbus address mapped by Mitsubishi Fx 3S register PLC Register type Type of data Type of data Device Mapping add...

Page 53: ...Output contact Q Q0 0 Q31 7 On off type 5000 5255 01 05 Timer contact TS T0 T255 On off type 10000 10255 01 Counter contact CS C0 C255 On off type 12000 12255 01 State relay S S0 0 S31 7 On off type...

Page 54: ...000000000000 10014 Reverse active peak power 32bit int kWh Y X 100 000000000000 10016 Reverse active power level 32bit int kWh Y X 100 000000000000 10018 Reverse active valley power 32bit int kWh Y X...

Page 55: ...Y X 1000 000000000000 10056 Instantaneous B phase reactive power 16bit int KW Y X 1000 000000000000 10057 Instantaneous phase C reactive power 16bit int KW Y X 1000 000000000000 10058 Total power fac...

Page 56: ...er point 32bit int kWh Y X 100 000000000000 14 Positive peak active power 32bit int kWh Y X 100 000000000000 16 Positive active power level 32bit int kWh Y X 100 000000000000 18 Positive active valley...

Page 57: ...int KW Y X 10000 000000000000 65 Instantaneous C phase active power 32bit int KW Y X 10000 000000000000 67 Instantaneous total reactive power 32bit int KW Y X 10000 000000000000 69 Instantaneous phas...

Page 58: ...ve power 32bit int KW Y X 10000 000000000000 90 Current total maximum demand for reverse active power 32bit int KW Y X 10000 000000000000 92 99 Reserved address 000000000001 100 Combination 1 total ac...

Reviews: