_________________________________________________________________________________________
Page 13 of 15 King Pigeon Communication Co.,Limited. Ver 1.5 File No.:RTU5025103
A Professional GSM 3G M2M products manufacturer
and automation solution provider, since 2005.
www.GSM-Gate-Opener.com Support@GSM-Gate-Opener.com
6.5 Others:
6.5.1 Power failure alarm (unit:minute)
xxx=000~999
xxx=000: power failure alarm SMS to the 1
st
number once the AC/DC power supply lost.
xxx=999: default, no power failure alarm SMS to be send.
6.5.2 Self-check auto report SMS to the 1
st
number. (unit:hour)
xxx=000~999
xxx=000, default,no self-check auto report.
Auto report SMS including:
Arm/Disarm Status;
DIN1/2 status;
Relay status;
GSM signal value(full is 31,cellular signal weak if lower than 14)
AC/DC power supply status.
Inquiry the self-check and auto-report time
6.5.3 Inquiry current status
6.5.4 Inquiry the historical data through SMS
Eg:
1234L#150101#150105#
to inquiry the historical data from Janurary 1 to Janurary 5,2015.
6.5.5
Inquiry the GSM modules’ IMEI code and firmware version
6.5.6 RESET the password
Press and hold the RESET button(closed to the SIM card holder), then power ON,after 6 seconds later, the
RTU5025 will restart,then release the RESET button.
This operation will reset the password to default 1234 only, other parameters reset must be reset by PC software.
6.5.7 Device ID
RTU5025 will create an ID according to the SIM Card number(the last of 8 digits).
pwdT#
pwdACxxx#
pwdT#xxx#
pwdEE
pwdL#yymmdd#yymmdd#
pwdIMEI#