www.kingsbottle.com
13
OPERATION
COMPRESSOR WINE CELLAR
PAR
RANGE
DESCRIPTION
Preset Value
SCL
1°C;
2°C;
°F
Readout scale.
1°C (with
INP
=SN4 only): measuring range -50/-9.9 … 19.9/80°C
2°C : measuring range -50 … 120°C
°F : measuring range -55 … 240°F
Caution: upon changing the
SCL
value, it is then absolutely necessary to re-configure the parameters
relevant to the absolute and relative temperatures (
SPL
,
SPH
,
SP
,
ALA
,
AHA
, etc..).
°F
SPL
-50..SPH
Minimum limit for
SP
setting.
41
SPH
SPL.120°
Maximum limit for
SP
setting.
64
SP
SPL... SPH Setpoint (value to be maintained in the room).
59
C-H
REF; HEA
Refrigerating (REF) or Heating (HEA) control mode.
REF
HYS
1...10°
OFF/ON thermostat differential
Refrigerating control (
C-H
=REF) Heating control (
C-H
=HEA)
5
CRT
0...30min
Compressor rest time. The output is switched on again after
CRT
minutes have elapsed since the
previous switchover. We recommend to set
CRT
=03 with
HYS
<2.0°.
6
CT1
0...30min
Thermostat output run when probe T1 is faulty. With
CT1
=0 the output will always remain OFF.
3
CT2
0...30min
Thermostat output stop when probe T1 is faulty. With
CT2
=0 and
CT1
>0
the output will always be ON.
Example:
CT1
=4,
CT2
= 6: In case of probe T1 failure, the compressor will cycle 4 minutes ON and 6
minutes OFF.
6
CSD
0..30min
Compressor stop delay after the door has been opened (active only if
DS
=YES).
6
DFR
0... 24(1/24h)
Defrost frequency expressed in cycles/24 hours.
3
DLI
-50...120°
Defrost end temperature.
39
DTO
1...120min
Maximum defrost duration.
20
DTY
OFF;
ELE;
GAS
Defrost type
OFF: off cycle defrost (Compressor and Heater OFF).
ELE: electric defrost* (Compressor OFF and Heater ON).
GAS: hot gas defrost* (Compressor and Heater ON).
* The defrost output is active if only
OAU
=DEF.
OFF
DRN
0...30min
Pause after defrost (evaporator drain down time).
0
DDY
0...60min
Display during defrost. If
DDY
=0 during defrost the temperature continues to be displayed. If
DDY
> 0,
during defrost the display shows DEF, and at the end of defrost it shows REC for
DDY
minutes.
1
FID
NO/YES
Fans active during defrost.
YES
FDD
-50...120°
Evaporator fan re-start temperature after defrost.
32
FTC
NO/YES
Optimised fan control enabling. With
FTC
= NO the fans remain on all the time.
Fig. 2 Optimised fan control (
FTC
=YES)
YES
FT1
0...180sec
Fan stop delay after compressor stop. See Fig. 2.
180
FT2
0...30min
Timed fan stop. With
FT2
=0 the fans remain on all the time.
1
FT3
0...30min
Timed fan run. With
FT3
=0, and
FT2
> 0, the fans remain off all the time.
1