SPECIFICATION
MAINTENANCE
Servicing should only be carried out after the luminaire has been made electrically safe.
Lamps should be replaced at set intervals for maximum system integrity, use only lamps of the
correct type and rating and follow the lamp manufacturers instructions.
Cleaning should be carried out at regular intervals to ensure that dirt does not accumulate to an
extent that will impair the electrical and / or thermal safety of the luminaire. Regular cleaning will
also ensure that the optical performance is maintained.
Battery packs should be replaced when the luminaire fails to meet its rated duration, regardless all
batteries must be replaced after
4
years service.
The disposal of components from the luminaire may require consultation with local authorities.
The disposal of batteries is subject to Local Authority Regulations, and the By-Laws Department
for disposal of toxic waste should be consulted for specific guidance. Battery cell packs must not
be incinerated. Do not dispose with household waste, subject to conditions in the WEEE directive.
Audible Alarm
•
Battery failure:
One repeated beep
•
Illumination Failure:
Repeated two beep cycle
•
Auto test failure:
Repeated three beep cycle
Auto Fault Monitoring
When connected to the mains supply and a system fault is detected, the audible alarm will sound
continously for the first
10
minutes and the failure/charging indicator will flash. After
10
minutes
the alarm will beep once every minute for the next hour. After the first hour it will beep every
twenty minutes upto twenty four hours. After this the alarm will cease and the fault indicator will
flash only.
Auto-test Switch
• Manual Test:
Press the button on the PCB for
3
seconds, the emergency light will come on for
5
minutes to check illumination.
• Auto Test:
Press the button for
1
second, this initiates the ‘Auto Test’ sequence. The emergency
light will light automatically once every
90
days for test duration of
1
hour. If the fitting fails to
light for
1
hour the audible alarm will give a three beep sequence as mentioned in the audible
alarm section above. If the
1
hour test is satisfactory the fitting will return to normal operation.
5.
Mark the battery cell pack with the date of installation and connect the battery.
6
. Refit the front cover, taking care to ensure that no wires are trapped and that all fastenings are
secure.
7
. To adjust the position of the lamp heads, loosen the axis screws before positioning so as not
to cause excess strain on the lamp fixings.
WARNING
The battery cell pack must be CONNECTED before the mains is switched on.
Failure to comply with these installation instructions may result in irreparable damage to the
main circuit.
DO NOT HIGH-VOLTAGE INSULATION TEST THIS UNIT, OR THE LIGHTING SYSTEM WITH
THIS UNIT CONNECTED.
COMMISSIONING & TESTING
Class I. This product must be earthed.
Terminal (L):
This is the live supply to the charging circuit and must be permanent
and unswitched.
Terminal ( E):
This is for the earth and must be connected.
Terminal (N):
This is the neutral supply and must be permanent.
Colour code:
Brown=Live
Blue=Neutral
Green/Yellow=Earth
Conductor Space Size
1.0
mm
2
-
2.5
mm
2
Solid or Stranded.
Ensure that no strands of bare wire have escaped the terminals.
4
. Bring the cable into position and make the correct electrical connections as follows:
Note: The ELTSLED
65
NM uses screwless terminals.
NON-MAINTAINED
NEUTRAL
(BLUE)
PERMANENT LIVE
(BROWN)
E
N
L
EARTH
GREEN/YELLOW
Input Voltage:
220/240
V AC,
50/60
Hz,
3.2
W
LED Power:
4.7
W,
93.8
lm/W
Fuse installed or replacement:
0.5
A,
250
VAC
Battery Installed or replacement:
3.6
V
/6
Ah Ni-Cd
LED Built-in:
LED
54
+
54
pcs
IP Rating:
IP
65
Operating Environmental Temperature:
0
°C -
40
°C
Re-charging Time:
24
hours
Emergency Duration:
More than
3
hours
Switch on the mains supply, check that ‘Charge ON’, ‘Lamp
1
’ and ‘Lamp
2
’ green LED
indicators are lit.
Allow a brief time for initial partial charging and then isolate the permanent live supply by
removing the fuse from the fused spur box. Check to ensure the lamps are illuminated from the
battery cell pack supply. After a further
60
hours on a continuous charge, and only at a safe and
appropriate time, mains failure should be simulated to ensure that full duration rating is
achieved. Thereafter the recharge time is
24
hours.
Function of LED Indicators
1
.
Auto test indicator
2
.
Failure/charging indication
3
.
Lamphead
1
indicator
4
.
Lamphead
2
indicator
1
.
2
.
3
.
4
.