ZCV34
Installation of Side Wall Venting
1.
To determine the minimum distance from the bottom of fireplace to center of vent see the Framing Your Gas Fireplace
section. Cut a hole through the wall allowing for an 11” x 11” (inside diameter) in
combustible walls for wall thimble or an
8” diameter hole in a non
-combustible wall (See Figure 2).
2.
For the clearance to combustible above a 90-degree bend see Clearance to Combustibles section.
3.
Select the approximate vent length, precise measurements are not needed as your flex pipe can be expanded to twice its
shipped length for ease of installation.
4.
To install wall thimble center over 11” x 11”
(inch) framing from
both sides of wall and secure. Route flex vent pipe through wall
thimble (See Figure 1).
5.
Before joining pipes, apply a bead of high temperature sealant
(Mill Pac) to end of pipe. First attach the four-
inch (4”) flue pipe to
the vent termination with sealant, and secure with the four screws
provided. At this time make sure the spacer springs are attached to
the (4”) flex pipe as required. Then attach the seven
-
inch (7”) pipe
by the same method.
6.
Mount vent termination and seal to wall using caulking around the wall thimble to weather proof. After installing the vent
termination, double check to make sure the pipe extends properly through wall thimble and into vent termination.
7.
Before joining pipes to fireplace flue, apply a bead of high temperature sealant (Mill Pac) to end of pipe. First attach the
four-
inch (4”) flue pipe to fireplace with sealant, and secure with the four screws provided. At this time verify that the
spacer springs are attached properly to the (4”) flex pipe as required.
Then attach the seven-
inch (7”) pipe by the same
method.
8.
Support horizontal pipes every two (2) feet (61 cm) with metal strap bands. Re-check fireplace to make sure it is levelled
and properly positioned and secured.
9.
Support vertical pipes to maintain a m
inimum of 1” or greater clearance to combustibles with metal strapping bands.
10.
If finishing the outside wall with vinyl or wood siding it is recommended that a Siding Shield be installed, Part Number
ZDVSSLR.
Note: Vent Termination must not be recessed into wall or siding.
WARNING:
A HORIZONTAL VENT CERTIFIED GUARD (SAFETY CAGE) IS AVAILABLE WHEN REQUIRED BY LOCAL CODES.
MIN 40
” FOR
NG
MIN 52” FOR
PROPANE
THROUGH NON-COMBUSTIBLE WALL
THROUGH COMBUSTIBLE WALL
MINIMUM 1” TO
COMBUSTIBLES
Figure 1
Figure 2
MIN 40
” FOR
NG
MIN 52” FOR
PROPANE
Z58WTS Wall Thimble
Shield -
Must be used for
Non-Vented enclosures
with horizontal venting.
ZDVWT Wall Thimble
FDVHT -
Horizontal Vent
Termination
79