Approved for Power Vent PVH58 / PVH58FM
- This appliance is approved for use with Kingsman Horizontal Power Vents -
A Horizontal Power Vent Termination is intended for use where standard venting configurations are
not possible.
NOTE:
MODELS EQUIPPPED WITH MILLIVOLT/ STANDING PILOT IGNITION: Downward vertical vent runs are
NOT
permitted.
NOTE:
MODELS EQUIPPPED WITH INTERMITTENT PILOT IGNITION (Proflame 1 or Proflame 2):
Downward vertical vent runs are permitted, however, Cold Climate Switch (Standing Pilot Mode) must
NOT
be used.
Refer to Power Vent Manual for proper installation and use.
ENCLAVE MQVL60 / MQVLBG60 Maximum & Minimum Vent Lengths using Power Vents:
Minimum Vent Length
is 4 FT vertical x 6 FT horizontal with up to 5 elbows.
Maximum Vent Length
is 4FT vertical x 125FT horizontal
with up to 7 elbows.
PVH58
PVH58FM
78