KINTECH ENGINEERING
ORBIT 360 | USER GUIDE
133
10.3
Modbus types
Acciona: Adaptation to SCADA WinCC (Siemens), adds compatibility to Acciona
SCADA.
Suzlon: Adaptation to SCADA SC-METSTATION (Suzlon Energy - legacy data
logger Modbus telegram). It is configured at type 27 (baudrate: 9600). EOL Zenith
data logger receives a request (register count: 10d) and the answer (register
count: 20d) contains these values in 16 bits integer format:
40001: anemometer 1.
40002: constant 9999d (Before legacy not implemented).
40003: windvane 1.
40004: temperature sensor. It must be Galltec KPC1/5 (Slope: 100 – Offset:
-30). This sensor has to be configured between analog channel 1 and
analog channel 5 (logger takes the first temperature sensor on this
range).
40005: pressure sensor. This sensor has to be configured between analog
channel 1 and analog channel 5 (logger takes the first pressure sensor on
this range).
40006: constant 9999d.
40007: humidity sensor. This sensor has to be configured between analog
channel 1 and analog channel 5 (logger takes the first humidity sensor on
this range).
40008: rain sensor. It must be configured as voltmeter. This sensor has to
be configured between analog channel 1 and analog channel 5 (logger
takes the first voltmeter on this range).
40009: met station. Logger status.
40010: constant 0d