![background image](http://html1.mh-extra.com/html/kipor/kp310v1-0/kp310v1-0_operation-manual_1971704019.webp)
KP310V1.0 Controller Operation Manual
- 17 -
13 Preheat
delay
○○●●○●
0-100 0.1s
50
Set Output 1 or Set Output 2 is
setted as “ Genset Preheat ”, it
works when genset starts,
controller start to count down..
14 Safety
Delay
○○●●●○
20-255
0.1s
60
Within the safety delay, under oil
pressure, high water temperature,
under speed
、
under voltage
、
under frequency
、
charging fault.
Generator
15
Phase Type
○○●●●●
0-4
1
0
0-
3-Phase 4-Line/3P4L
1-
3-Phase 3-Line/3P3L
2-
1-Phase 2-Line/1P2L
3-
Double voltage
4-
Double voltage select
16 Current
Ratio
○●○○○○
1-65535 1A/5mA
50
External CT ratio
17
Under
Frequency
○●○○○●
0-800 0.1Hz 450
18 Over
Frequency
○●○○●○
0-800 0.1Hz 550
19 Under
Voltage
○●○○●●
0-5000
0.1V 2050
20 Over
Voltage
○●○●○○
0-5000
0.1V 2450
21 Over
Current
1
○●○●○●
0-65535
0.1A
450 Generator
pre-overload
22 Over
Current
2
○●○●●○
0-65535
0.1A
500 Generator
overload
23
Under
Frequency Fault
Delay
○●○●●●
0-65535
0.1S
20
Generator output under frequency
Stop Delay
24
Over Frequency
Fault Delay
○●●○○○
0-65535
0.1S
5
Generator output over frequency
Stop Delay
25
Under Voltage
Fault Delay
○●●○○●
0-65535
0.1S
20
Generator output voltage low Stop
Delay
26
Over Voltage
Fault Delay
○●●○●○
0-65535
0.1S
5
Generator output voltage high
Stop Delay
27
Over Current 1
Fault Delay
○●●○●●
0-65535
0.1S
600
Genset pre-overload delay timing
28
Over Current 2
Fault Delay
○●●●○○
0-65535
0.1S
50
Genset overload delay timing
29
Over Current 1
Stop Delay
○●●●○●
0-65535
0.1S
300
Genset pre-overload stop delay
timing
30
Over Current 2
Stop Delay
○●●●●○
0-65535
0.1S
300
Genset overload stop delay timing
Battery
31 Under
Voltage
○●●●●●
0-400 0.1V 100
Battery voltage under voltage
alarm
32 Over
Voltage
●○○○○○
0-400
0.1V
180
Battery voltage over voltage alarm