25
AC voltage and current may bring electric shock hazard and cause serious personal injury or even
death. Please make sure both the AC power supplies have been cut off.
KPEC series ATS cabinet can start and monitor the operation of generator set, so it is necessary to
connect the control cable of ATS cabinet and generator set.
There are 2 kinds of connection mean for control cable: connection terminal type and quick
connector type. Control cable is different from each other according to the various model of
generator set.
Connection terminal type (terminals) control cable is marked with wire number (section area: 1.0m
㎡
. The length can be optional according to the onsite installation location, with recommended value
10m). During operation, users need to connect one cable terminal to relevant same-line terminal
block on generator set (refer to “Electrical principle diagram of generator set” for connection
terminal size), and the other terminal to same-line terminal block X1 on ATS cabinet (refer to
“Electrical principle diagram of ATS” for connection terminal size).Wiring diagram of ATS cabinet
please see the attachment of Part 6.
Both the terminals of quick connection type (quick connector) control cable ( section area: 1.0m
㎡
.
The length can be optional according to the onsite installation location, with recommended value
15m) are ready made quick connect plugs with their sockets on the generator set and the ATS.
When using it, users only need to plug the terminals of control cable and quick connectors of
generator set and ATS cabinet into their sockets and screw them down.
¾
Check and clean
·Check all the circuit, make sure:
- The circuit and the switch do not interfere in each other.
- There is no broken wire at the switch of cabinet door.
- The circuit is not exposed to keen-edged or abrasive surface.
- There is no line loosen or disconnection.
·After mounting and wiring the cabinet, clean the internal cabinet and remove all the debris, filings
and filth inside the cabinet and on the parts.
·Recheck the power voltage, make sure it coincide with the ratings on nameplate.
·Recheck the power phase, make sure the grid phase identical with that of generator set.
·Make sure control cable of ATS cabinet is correctly connected to that of generator set.
·Cut off power and operate ATS, make sure the operation is stable and free of cumber. If it is not,
check if there is damage caused by transportation or mounting, or if any chips are generated in
installation.
3.5 Operation
Summary of Contents for KPEC Series
Page 1: ...1 KPEC Series User Manual of ATS Cabinet www kipor com...
Page 38: ...6 Attachment 1 Electric principle figure four figures together...
Page 39: ......
Page 40: ...2 User wiring diagram six together...
Page 41: ......
Page 42: ......
Page 43: ...3 Definition of ATS cabinet remote control aviation plug option...