28
Data Unit
Pre-setting
value
Description
Failure start
Sec
10
Fixed parameter, unchangeable
3. Generator
Data Unit
Setting
Range
Pre-setting
value
Description
Freq Low
1Hz
-20%
50Hz:400;60Hz:480
Freq High
1Hz
+14%
50Hz:570;60Hz:684
Vol Low
0.1V
80
%
~90
%
-10%Ue
Includes disengage and return value
Vol High
0.1V
105
%
~130
%
+10%Ue
Includes disengage and return value
4. Main
Data Unit
Setting
Range Pre-setting
value
Description
Freq Low
1Hz
(-24%)/ (-14%)
50Hz:380/430;60Hz:456/516
Freq High
1Hz
(+24%)/ (+14%)
50Hz:620/570;60Hz:744/684
Vol Low
0.1V
80
%
~90
%
-10%Ue
Includes disengage and return value
Vol High
0.1V
105
%
~130
%
+10%Ue
Includes disengage and return value
5. ATS
Data Unit
Pre-setti
ng Value
Description
ReStart Cnt
Time(s)
3
Fixed parameter, unchangeable
Time lag of grid returning to be
normal
Sec 30
Can be set as 0s, 5s, 10s, 20s, 30s, 60s,
180s
Time lag of generator
preheating
Sec
5
Can be set as 0s, 1s, 2s, 3s, 4s, 5s, 6s, 8s
Time lag of generator warming
Sec
30
Can be set as 0s, 1s, 2s, 3s, 5s, 30s,
120s, 300s
Time lag of voltage transfer
Sec
2
Can be set as 0s, 1s, 2s, 3s, 4s, 5s, 8s,
10s
Time lag of generator cooling
Min
2
Can be set as 0m, 0.1m, 2m, 5m, 10m,
15m, 25m, 30m
Data has been set up before delivery, adjustment is unnecessary. Users can't modify the data
under default mode! Please contact nearest dealer first if you would like to modify the data.
Maintenance personnel will service you at any moment.
As to details of KPD100 controller, please refer to operation manual of KPD100 controller.
3.6 Trial run of ATS cabinet
Summary of Contents for KPEC Series
Page 1: ...1 KPEC Series User Manual of ATS Cabinet www kipor com...
Page 38: ...6 Attachment 1 Electric principle figure four figures together...
Page 39: ......
Page 40: ...2 User wiring diagram six together...
Page 41: ......
Page 42: ......
Page 43: ...3 Definition of ATS cabinet remote control aviation plug option...