2-3-4 Installing flue (Plume Displacement)
Content of kit
1 0.9m 60/100 Concentric Flue
1 1m 60 Dia-meter Exhaust Flue Pipe
1 Adaptor
2 60Dia Support Brackets
1 93
˚
Elbow/Plume Outlet Assembly
1 Flexible Flue Time
3 "O" Rings
1 Jubilee Clip
1 Elbow
1. This kit is recommended for installations where the condensate
plume emitted from the flue may cause a nuisance or affect the
surroundings.
2. The terminal must be positioned outside the building with the air
inlet facing downward and outlet connection upwards.
3. The plume outlet must always be at least 45
˚
to the wall with
the '' uppermost to prevent rain entry (Fig. 15 & 16)
and be at least 2 meters above ground level. It must be at least
500mm from the air inlet in any direction (Fig. 16)
NOTE :
The outlet must be positioned so that any condensate
plume is directed away from adjacent surfaces. There must be a
constant fall along the entire of the flue system from the back to
boiler
4. It is possible to reduce or increase (with the addition of
extensions) the length of either or both 60/100 concentric and 60
Φ
exhaust.
5. Standard concentric flue extension kits may be added between
the boiler elbow the terminal assembly
6. The minimum length of the concentric flue is 100mm when measured
from the edge of the flue elbow
IMPORTANT :
The maximum equivalent length of concentric
flue is :
8 meters
Additional bends may be fitted in the concentric flue, but the equivalent
length must be reduced I meter (93
˚
elbow) or 0.5 metric
(45
˚
elbow)
7. 60
Φ
I meter extensions (including support bracket), and additional
93
˚
& 45
˚
elbows are available. Any additional 93
˚
& 45
˚
elbows
must be accounted for when calculating flue lengths
11페이지