- 8 -
Installation
■
Applicable B oilers
The following requirements of the boiler shall
be satisfied:
1. The static pressure inside the burning
chamber shall be kept at 5 mmAq during the
rated burning of the boiler.
2. The minimum space of the combustion
chamber for mounting the burner shall be as
follows:
3. Though the burner may be mounted on the
body of the boiler for oil burning, the boiler
must have an hole for cleaning the combustion
chamber without disassembling the burner.
4. E very door installed for the maintenance of
boiler shall be airtight.
Requirements for the Boiler R oom
■
The boiler room
has an opening for supplying
outdoor air into the room to
feed sufficient air to the burner.
The siz e of the opening shall be equal to
or larger than the cross section of
the chimney.
■
How to Assemble the Burner
1. The surface for mounting the burner shall
accommodate a hole with the following
dimensions for connecting the burner (M8 x
40 mm bolts shall be welded on the hole of
ø9 facing forward):
2. Assemble the flange gasket and the burner
on the burner hatch as shown in the figure
below.
Fasten the burner with M8 nuts and adjust
the burner to the left and right to keep the
burner horizontal.