Operating Instruction
Healthcare chiller of the KSC Series
Version „Revision 09“
Type KSC 215-L-U/S
page 126von138
\\FILER02\Allgemein\02 - Technische Unterlagen KKT\Originale\830xxx Bedienungsanleitungen\KSC\83002302.Ka KKT chillers_KSC215-US.doc
11.13
Safety valve
Diaphragm safety relief valve
531 series ¾
”
- 1
”
Diaphragm safety relief valve for potable water
systems, with female-female connections.
Factory set at: 6 bar.
Maximum opening pressure: +10%.
Minimum reseating pressure: -20%.
Maximum temperature: 100°C.
Brass body.
Diaphragm and seal in EPDM.
Cover and handle in glass reinforced nylon.